By default, I-Link device is set to accept maximal CT output voltage of 4V. Anyway, on special
request, it can be set to accept 8V: this must be specified when ordered.
At this present moment, LEM recommends the following current sensors.
- For use with cables:
HTA
family : 32mm round aperture, available in 100, 200, 300, 400, 500, 600 and 1000 A
versions.
HTR
family : split-core for retrofit applications. Available in 50, 100, 200, 300, 400 and 500 A.
- For use with bus bars:
HAX
family : large 64 x 21 mm rectangular aperture. Available in 500, 600, 850, 1000, 1200,
1500, 2000 and 2500 A versions for larger applications.
HOP
family : rectangular aperture and split-core for retrofit. Available in 500, 800, 1000, 1500
and 2000 A versions
All the data sheets are available on LEM web-site.
2.4 S-Bus converter
The S-Bus converter is designed to convert the LEM proprietary Sentinel & I-Link
communication bus (S-Bus) to RS232 interface. Note, the module only acts on signal levels
conversion, no software protocol translation is performed.
The 25-pin connector is a standard (RS232) configuration and may be directly connected to
the serial port of a personal computer. Additional input power supply (7-12V), 500 mA min is
required.