2 GENERAL DESCRIPTION
The system is composed of Sentinel transducer modules, connected to every bloc being
monitored, linked together by S-BUS communication. Float and discharge current sensors are
interfaced via the I-Link module.
Only use the accessories supplied with such devices, specifically available for your equipment
(see table below).
DESCRIPTION
PART (CLEM) Numbers
Sentinel 2 - LV, 2V
66.61.05.000.0
Sentinel 2 - HV, 6-12V
66.61.14.000.0
I-Link 2
66.82.98.000.0
S-Bus converter
66.81.98.001.0
BM Cable power 0.25m
66.30.98.007.0
BM Cable power 0.4m
66.30.98.017.0
BM washer 06mm
66.30.98.013.0
BM washer 08mm
66.30.98.014.0
BM washer 10mm
66.30.98.015.0
BM washer 12mm
66.30.98.016.0
BM Cable comm 0.4m
66.30.98.001.0
BM Cable comm 1.0m
66.30.98.002.0
BM Cable comm 2.0m
66.30.98.003.0
BM Cable comm 5.0m
66.30.98.004.0
BM Cable comm 10m
66.30.98.005.0
BM Cable comm 15.0m
66.30.98.009.0
The Sentinel modules are connected to the bloc by Power & Sense leads, with available
connection lengths: 250mm or 400mm.
Special Kelvin washers (0.8 mm thick) are available and must be used to connect the power &
sense
leads to the blocs in order to insure correct bloc impedance measurements.
S-Bus and I-Bus link are via RJ10 pre-terminated communication cables. Available
communication lengths are: 400mm, 2m, 5m, 10m, 15m.
The Sentinels units are daisy-chained on S-Bus, as well as I-Links modules (if more than one
unit is used) on I-Bus.