Relay Test
The relay test will allow the user to temporarily control a relay. Relay status
LEDs will track the control state.
Press
Enter
at the
control
menu, the
Clear memory
menu is displayed.
Press the
Up
button twice to display the
relay control
menu.
Press
Enter
to display the
relay
list item.
Use the
Up
and
Down
buttons to select a relay to control. Press the
Sel
button to toggle the relay ON or
OFF. The apostrophe LED will be lit when the relay is turned ON.
Press
Menu
to exit. See Menu navigation.
Ramp Test
The ramp test can be used to test 0-10V outputs as well as the associated relays. Relay status LEDs will
track the control state.
Press
Enter
at the
control
menu, the
Clear memory
menu is displayed.
Press the
Up
button thrice to display the
ramp
menu.
Press
Enter
to start ramp test, loops thru each output ramping to full, then off.
The ramp test screen indicates the current output that is ramping.
Press
Menu
to exit and end ramp test.
Relay Override
Use relay override to turn on zone relay, bypassing all inputs. Relay status LEDs will reflect the override
state.
Press
Enter
at the
control
menu, the
Clear memory
menu is displayed.
Press the
Down
button thrice to display the
relay override
menu.
Press
Enter
to display the
override relay
list control.
Use the
Up
and
Down
buttons to select a relay to control.
Press the
Sel
button to toggle the relay ON, OFF, or release override.
The apostrophe LED will be lit when the relay is turned ON.
The 2
nd
digit decimal point is lit when the relay is off.
Neither lit indicates the relay is released from override.
Press
Menu
to exit. See Menu navigation.