29
E-Flex User Manual, Rev. 1.30
Control/Test
Navigate to Control menu
Press
Menu,
inpX
menu is displayed.
Press the
Down
button to scroll to the
control
menu.
Clear Memory
Press
Enter
at the
control
menu, the
Clear memory
menu item is displayed.
Press
Enter
to be able to clear memory and reset to factory defaults.
You will be prompted to make sure you wish to clear memory.
Press
Sel
to actually clear memory or press
Menu
to return to previous level
and not clear memory.
On
Sel
, the relay panel will reset all configuration data to defaults and restart. You will see the firmware
version on the display followed by the default data version.
DMX Loss Behavior
Press
Enter
at the
control
menu, the
Clear memory
menu is displayed.
Press the
Up
button to display the
DMX loss
list control.
Press
Enter
to show the first item in
DMX loss options
list. The current
programmed option will be displayed first.
Use the
Up
and
Down
buttons to display the available options:
Opt1
– None, return control to other inputs (default).
Opt2
- Go to off.
Opt3
– Go to 100%.
Opt4
– Go to preset 18*.
Press
Sel
to choose the displayed option. The apostrophe LED will be lit for the current programmed
option. Press
Store button
to record the new setting.
Opt 1 is the default setting and is typical for stage applications where a lighting console takes control of
all theater lighting when it is running, and returns control to the architectural or house lighting controls
when the console is turned off.
Opt 3 and 4 are more typical for architectural applications to ensure that on loss of signal from a DMX-
based architectural controller that there are lights on. Option 4 allows editing of a preset to set zone
light levels and which zones are on or off.
*preset 18 is dedicated to DMX loss, use preset editor to set levels as desired.