12
E-Flex User Manual, Rev. 1.30
SW5 – FlexNet Termination
Default OFF, set to ON for each end of line device. Should only be two end-of-line devices in a
system.
SW6 – DMX Termination
Default OFF, set to ON for each end of line device. Should only be two end-of-line devices in a
system.
Emergency Input
The Emergency UL924 contact input requires a normally closed contact that will open upon loss of
normal power. When the emergency input is activated (opened) the following can be expected for each
output of the relay panel:
For outputs that are assigned to the emergency input, the relay will close and the 0-10V output
will be driven to 100%.
Outputs not assigned to the emergency input will remain at their current level.
Emergency Enable/Disable (EMERG-J12)
Jumper J12 (EMERG) is used to enable or disable the emergency input. To enable, position the jumper
across J12 pins 1-2. To disable (default) position the jumper across J12 pins 2-3.