Adjusting the Light Level

This feature is factory set at maximum, so that even the brightest light will not 
prevent the sensor from turning the load ON when it detects occupancy. If this 
feature is not needed, leave the light level at maximum, fully clockwise.

1.  The light level must be adjusted when lights would normally be turned OFF 

because there is enough natural illumination.

2.  Set the sensor to Mode 2 and reduce the time delay to 15 seconds.

3.  Adjust the light level to minimum. Let the sensor time out so lights are OFF 

and then wait 30 seconds more.

4.  Without casting a shadow on the sensor, enter the area. The lights should 

remain OFF.

5.  Adjust the light level trimpot clockwise in small increments. Wait 5-10 seconds 

after each adjustment to see if the lights turn ON. Continue this procedure 
until the lights turn ON. At this setting the lights will not turn ON automatically 
with occupancy if the light level is above the current natural illumination.

6.  Reset the time delay to the desired setting.

Warning: Do not overturn the light level adjustment trimpot!

TEST MODE

To test the detection coverage:

During the TEST mode, the controlled load turns ON for 5 seconds each time the 
sensor detects occupancy.

1.  Press and hold the ON/OFF button. After 10 seconds the nightlight fl ashes. The 

load turns ON if it was not already ON. The sensor is now in a TEST mode that 
lasts 5 minutes. (You can end the TEST mode sooner by pressing the ON/OFF 
button for another 10 seconds).

2.  Move out of the coverage area or stand very still. The controlled load turns OFF 

after 5 seconds if no motion is detected.

3.  Move into the coverage area. The controlled load turns ON for 5 seconds 

each time the sensor detects motion. After 5 seconds expire without motion 
detection, the load turns OFF. The controlled load turns ON automatically with 
the next motion detection and stays on for 5 seconds.

4.  Repeat as necessary to ensure that the desired coverage areas are within 

detection range.

TROUBLESHOOTING

Nightlight is OFF, no load response to ON/OFF button press:

•  Make certain that the circuit breaker is on and functioning.

Nightlight is ON, no load response to ON/OFF button press:

•  Check the light bulb and/or motor switch on the fan mechanism.

Load will not turn ON automatically when the area is occupied and the 
sensor is in Mode 2 (nightlight is ON): 

•  Press ON/OFF button. If the load turns ON, check the light level setting and 

also make sure the sensor lens is not blocked. The light level can prevent the 
sensor from turning on the load automatically.

•  If the load does not turn ON when you press the ON/OFF button, check the light 

bulb and/or motor switch on the fan mechanism.

Load will not turn OFF automatically:

•  Press ON/OFF button. If the controlled load turns OFF, go to next step.

•  The time delay can be set from 30 seconds to 30 minutes. Ensure that there is 

no movement within the sensor’s view for the set time period. Hot air currents 
and heat radiant devices can cause false detection. Make sure the sensor is at 
least 6 feet (2 meters) away from devices that are a signifi cant heat source (e.g. 
heater, heater vent, high wattage light bulb).

If load does not respond properly after following troubleshooting, turn OFF 

power to the circuit then check wire connections or call technical support.

Summary of Contents for WattStopper RS-250-N

Page 1: ...r Manual ON OFF Auto OFF The user must press the ON OFF button to turn the load ON The RS 250 N keeps the load ON until no motion is detected for the selected time delay period adjustable from 15 seco...

Page 2: ...e the switch box After the power is turned OFF at the circuit breaker box remove the existing wall plate and mounting screws Pull the old switch out from the wall box 2 Identify the type of circuit In...

Page 3: ...button Slide the button downward approximately 1 2 inch to expose the mode button and adjustment trimpots Setting up the Operating Mode Select the operating mode by pressing the Mode button The night...

Page 4: ...led load turns OFF after 5 seconds if no motion is detected 3 Move into the coverage area The controlled load turns ON for 5 seconds each time the sensor detects motion After 5 seconds expire without...

Page 5: ...on the part of Watt Stopper Legrand for consequential damages arising out of or in connection with the use or performance of this product or other indirect damages with respect to loss of property rev...

Page 6: ...encuentra encendida Cuando por el contrario la carga controlada se encuentra encendida la Luz Nocturna se encuentra apagada Modos de Operaci n Es posible elegir entre dos modos de operaci n durante l...

Page 7: ...e exista detecci n INSTALACION Y CABLEADO ADVERTENCIA Desconecte la corriente que alimenta la caja de conexiones apagando el disyuntor breaker o removiendo el fusible para el circuito correspondiente...

Page 8: ...ENCENDIDO APAGADO por ambos extremos y desl celo hacia abajo aproximadamente 1 2 pulgada de tal forma que el Bot n de Selecci n de Modos y las Perillas de Ajuste queden expuestas Selecci n del Modo de...

Page 9: ...n de ocupaci n si la cantidad de luz natural es mayor a la existente actualmente 6 Reajuste el tiempo de retardo de apagado al valor deseado Advertencia No sobregire la perilla de ajuste del Nivel de...

Page 10: ...apaga autom ticamente Presione el bot n de ENCENDIDO APAGADO Si la carga se apaga prosiga con el siguiente paso El tiempo del retardo de apagado puede ser con gurado desde 30 segundos hasta 30 minutos...

Reviews: