LEGRAND Wattstopper DSW-301 Installation Instructions Manual Download Page 1

Wattstopper

 

®

Dual Technology Multi-Way Wall Switch Occupancy Sensor
Interrupteur mural multiple à double technologie Détecteurs de mouvement
Interruptor de pared de múltiples vías con tecnología doble Sensores de ocupación

Installation Instructions • Instructions d’Installation • Instrucciones de Instalación

No: 29125 – 05/20 rev. 1

Catalog Numbers • Les Numéros de Catalogue • Los Números de Catálogo: DSW-301/DSW-302

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

Models ending in -U are BAA and TAA compliant (Product produced in the U.S.)

DESCRIPTION AND OPERATION

The DSW Dual Technology Multi-Way Wall Switch sensors combine advanced passive infrared (PIR) and ultrasonic technologies into 

one unit. The combined technologies help to eliminate false triggering even in difficult applications.
Selectable operating modes allow the sensor to turn a load 

ON

, and hold it 

ON

 as long as either or both technologies detect occupancy. 

It allows for up to 4 sensors to be connected to the same circuit. The first sensor to detect occupancy will turn 

ON

 all the lights that are 

connected to the same circuit. After the room is unoccupied, the last sensor that detected occupancy turns 

OFF

 all the lights once the 

time delay has expired. The occupant can turn 

OFF

 the load at any time by pressing the 

ON/OFF

 button of any sensor that is connected 

to the circuit. A “walk-through” mode can turn lights 

OFF

 after only 3 minutes if no activity is detected after 30 seconds following an 

occupancy detection.
The DSW-301 has one relay and one 

ON/OFF

 button. The DSW-302 contains two relays and two 

ON/OFF

 buttons to allow control of one or 

two loads independently. Pressing a button toggles the state of the corresponding relay. 
DSW sensors contain a light level sensor. If adequate daylight is present, the sensor holds the load 

OFF

 until light levels drop, even if 

the area is occupied. In the DSW-302, light level only affects the load on Relay 2. Users can override this function by pressing the  

ON/OFF

 button. See the Light Level Adjustment section.

Turning Load(s) ON (ON Mode)

The relays are programmed independently for either 

Auto ON

 or 

Manual ON

. In either mode, the load can be turned 

ON

 or 

OFF

 using 

the 

ON/OFF

 button.

Manual ON

DIP 8 

ON

 for Relay 1

DIP 9 

ON

 for Relay 2

With an 

ON Mode

 DIP switch in the 

ON

 position, the occupant must press the 

ON/OFF

 button to turn 

ON

 

the load. The sensor keeps the load 

ON

 until no motion is detected for the selected time delay. There is a 

30 second re-retrigger delay. If occupancy is detected during the delay, the sensor turns the load back 

ON

After the re-trigger delay elapses the 

ON/OFF

 button must be pressed to turn 

ON

 the load.

Auto ON 

DIP 8 

OFF

 for Relay 1

DIP 9 

OFF

 for Relay 2

With an 

ON Mode

 DIP switch in the 

OFF

 position, the load turns 

ON

 and 

OFF

 automatically based on 

occupancy. If the load is turned 

OFF

 manually, Presentation Mode operation applies. This prevents the load 

from turning 

ON

 automatically after it was deliberately turned 

OFF

. Pressing the button to turn lights 

ON

 

returns the sensor to 

Auto ON

 mode.

SPECIFICATIONS

Voltages ............................................................. 120/240/277 VAC, 50/60 Hz
Load Limits for relay 1:
 

@120 VAC ............... 1000-W tungsten, ballast, E-ballast, LED, 1/4 HP

 

@240/277 VAC ........................1200-W ballast, E-ballast, LED, 1/4 HP

Load Limits for relay 2:
 

@120 VAC ................. 800-W tungsten, ballast, E-ballast, LED, 1/6 HP

 

@240/277 VAC ........................1200-W ballast, E-ballast, LED, 1/6 HP

Time Delay Adjustment ......................................................... 5 to 30 minutes
Walk-Through Mode ...............................3 minutes if no activity after 30 sec.
Test Mode ...................................................... 10 min. with 5 -sec. time delay
PIR Adjustment ............................................................................High or Low
Ultrasonic Adjustment ........................................... Minimum to Maximum, Off
Ultrasonic Frequency ..........................................................................40 kHz
Light Level Adjustment .............................................................. 8fc to 180+fc
Alerts .................................................................. Selectable Audible & Visual
Signal Wire ................................................................................. Both models
Multi-Way Capability ................................................................... Both models

Summary of Contents for Wattstopper DSW-301

Page 1: ...level sensor If adequate daylight is present the sensor holds the load OFF until light levels drop even if the area is occupied In the DSW 302 light level only affects the load on Relay 2 Users can ov...

Page 2: ...he set time delay applies No Walk Through Walk Through Mode disabled This is the default PIR Sensitivity Adjustment The DSW sensor constantly monitors the controlled environment and automatically adju...

Page 3: ...the sensor After 10 seconds a beep sounds indicating that the threshold level is set This threshold is retained even if power is lost until it is re set or disabled In the DSW 302 light level control...

Page 4: ...e connects to Neutral For a replacement or retrofit application it can connect to Ground Load Red Black Neutral Line Green Ground Yellow Signal Blue w White Stripe Red Black Neutral Line Green Ground...

Page 5: ...nual On Relay 2 On Mode 4 High Low 50 PIR Sensitivity 7 Disabled Enabled Audible Alert 1 2 5 minutes Test 20 min 15 minutes 30 minutes Time Delay 5 6 Trigger Mode Initial Occupancy Maintain Occupancy...

Page 6: ...dard decorator style switch cover plates Cover plates are not included Units come in the following colors which are indicated by the final suffix of the catalog number shown here in parentheses White...

Page 7: ...des Si une pr sence se re d clenche lors de ce d lai voir la section Mode d clenchement le d tecteur R ACTIVE la charge la fin du d lai de re d clenchement il est n cessaire d appuyer sur le bouton MA...

Page 8: ...rasons L un ou l autre n cessite une d tection de mouvements par uniquement une technologie IRP n cessite une d tection de mouvements par l IRP Pr sence initiale la m thode qui active un changement de...

Page 9: ...nt 10 secondes jusqu l mission d un triple bip sonore Cette op ration r initialise le d tecteur et d sactive le contr le du niveau de luminosit la luminosit ambiante la plus intense ne maintiendra pas...

Page 10: ...nutes Temporisation Mode Mode Pr sence initiale Maintien de pr sence Option C Les deux Les deux 5 Standard L un ou l autre 5 L un ou l autre Option A L un ou l autre L un ou l autre 5 IRP Les deux Opt...

Page 11: ...he est s lectionn au niveau des interrupteurs DIP 8 et 9 2 Assurez vous que le contr le du niveau de luminosit est activ couvrez la lentille du d tecteur avec votre main Si les lumi res s ALLUMENT r g...

Page 12: ...mesure d accepter toute interf rence re ue y compris les interf rences qui peuvent causer un fonctionnement ind sirable REMARQUE Ce mat riel a t mis l essai et a t jug conforme aux limites d un dispo...

Page 13: ...1 Conmutador selector para bascular 9 ON para el rel 2 Con un conmutador selector para bascular en el modo activado en la posici n de encendido el ocupante debe presionar el bot n de Encendido y Apaga...

Page 14: ...nes de control en modo de encendido Ajuste de sensibilidad infrarroja pasiva PIR El sensor DSW monitorea constantemente el entorno controlado y ajusta autom ticamente el PIR para evitar las condicione...

Page 15: ...egundos suena otra se al sonora indicando que el nivel m nimo est configurado Este nivel m nimo se guarda aun cuando se corta la energ a hasta que se vuelve a configurar o se lo desactiva En el DSW 30...

Page 16: ...caci n de reemplazo o actualizaci n se puede conectar a Tierra Rojo Negro Neutro L nea Verde Tierra Azul Carga principal Carga secundaria Marr n Amarillo Se al Azul con franja blanca Rojo Negro Neutro...

Page 17: ...sensor establecido en modo de encendido manual o de reinicio instant neo para el sensor establecido en modo de encendido autom tico Una vez que transcurra la demora de reinicio debe presionarse el bot...

Page 18: ...nci metro no est apuntando a Servicio LED rojo encendido Si es as gire el potenci metro al valor medio apuntando hacia arriba La configuraci n del servicio permite a los usuarios hacer funcionar el se...

Reviews: