9. THERMAL MANAGEMENT
(continued)
9.2 1U ventilation drawers
(continued)
9.3 Thermostat
The mechanical thermostat Cat. No. 0 348 48 is used to control the
switching on/off of the fans in order to control the temperature inside
the cabinets.
Fans
Thermostat Cat. No. 0 348 48
Features
- IP20
- 230 V~ - 50/60 Hz
- Adjustment range +5°C to +60°C
- Switching range: 2°C
- NC contact: 5 A, 250 V~
- NO contact: 10 A, 250 V~
- Connection via 2.5 mm
2
terminal block
- Class N interfercab. suppression according to VDE 0875
- Magnetic mounting
- Black
51
37
68
It is essential not to exceed the following dual limit:
- 100 kg total weight installed on runners
- 570 mm projection
P 60
0
P 80
0
P 1000
P 600/800/1000
P 60
0
P 80
0
P 600/800
570
+
+
100 Kg max.
+…=
P 60
0
P 80
0
P 1000
P 600/800/1000
P 60
0
P 80
0
P 600/800
570
+
+
100 Kg max.
+…=
P 60
0
P 80
0
P 1000
P 600/800/1000
P 60
0
P 80
0
P 600/800
570
+
+
100 Kg max.
+…=
P 60
0
P 80
0
P 1000
P 600/800/1000
P 60
0
P 80
0
P 600/800
570
+
+
100 Kg max.
+…=
10. ACCESSORIES
10.1 Anti-tilt kit
The anti-tilt kit Cat. No. 0 464 84 stabilises a 19" LCS
2
freestanding
cabinet (which is not fixed to the floor) when heavy products installed
on telescopic equipment are removed.
The kit, which consists of 2 rails fixed under the lower end plate,
prevents the cabinet tilting forwards.
The kit can be mounted before or after installation of the cabinet.
The kit is suitable for all three cabinet depths:
To limit the projection of the rails at the front of the cabinet, another
type of mounting is possible for cabinets depth 600/800 mm:
(1)
Overall dimensions: +70 mm for back connection
150
300
75
75
150
43
43
1U
1U
(53 overall)
(53 overall)
19"
19"
442
442
60
60
200
200
(1)
(1)