310484 Modular Battery Cabinet Keor Mod
Installa
tion and main
tenanc
e manual
39
4. Push up the safety hook located on the left side of the battery drawer to unlock the block and pull the drawer to fina-
lize the extraction.
5. Follow the procedure shown at paragraph 4.3 to insert a new battery drawer
6. Exit from the UPS maintenance bypass mode (check the Keor MOD UPS installation manual)
5.3.3 Battery drawer fuses replacement
If there is the need to replace the fuses present at the back of the battery drawer, use only 14x51 fuses, gG type, 40A rated
In current, 500V rated voltage.