Keor MOD
Installa
tion and main
tenanc
e manual
37
5. Push up the safety hook located on the left side of the battery drawer to unlock the block and pull the drawer to fina-
lize the extraction.
6. Follow the procedure shown at paragraph 4.3 to insert a new battery drawer
INDICATION
If the UPS turns to battery mode during these operations, do not continue the installation/replacement. It is possible to
resume the operations when the UPS turns to on-line mode.
When there is a black-out during the replacement of battery drawers, the backup time is reduced. It is necessary to care-
fully assess this event before starting with the installation/replacement procedure.
To add a battery drawer:
Follow the procedure shown at paragraph 4.3 to add a new battery drawer