5.3.2 Installation/replacement of battery drawers with UPS in maintenance manual bypass
To replace a battery drawer:
1. Set the UPS in maintenance bypass mode (check the Keor MOD UPS installation manual)
2. Extract the battery drawer until the safety block prevents to continue the extraction.
3. Remove all the battery packs from the drawer. Use the handle included in the accessory kit to remove the battery
packs at the back of the drawer.
5. Maintenance