KNX 4 channels binary input interface

  7 . parameter Setting DeSCription in the etS

7 .1 parameter window“general Setting”

Parameter window “General Setting” can be shown in fig. 5.1. The 

function is used for limiting the number of sending telegrams to the 

bus, which can affect the complete device. The device initialization 

takes about 5s.

Fig.7.1 Parameter window “General Setting”

parameter“limit number of tele .”
It is used to limit the number of sending telegrams to decrease the 

burthen on the bus. It is possible to set how many telegrams can be 

sent within an adjustment period.

Options:   Yes 

No

When yes is selected in this parameter the Period and Max. Number 

Tele. Within a period parameters appear.

parameter “period”
The limit time of sending telegrams is set with the parameter.

Options:   300ms 

500ms 

 

10min

When device completes initialization in bus voltage recovery, start the 

observation period, and start count the sent telegrams. As soon as the 

Max. Number of transmitted telegrams has been reached, no further 

telegrams are sent on the bus until the end of the observation period. 

With the start of a new observation period, the telegram counter is reset 

to zero and the sending of telegrams is permitted again.
parameter “max . number tele . Within a period”
This parameter sets the number of telegrams which can be sent within 

an observation period.

Options: 1…255

7 .2 parameter window“manual/automatic Setting”

Parameter window“Manual/Automatic Setting”can be shown in fig. 

5.2. It is possible to switch between manual operation and automatic 

operation by pressing the manual/automatic button about 2s. 

When the manual/automatic operations are switched successfully, 

the manual/automatic LED will flash for three times. In the manual 

mode the manual/automatic LED is on. In the automatic mode the 

manual/automatic LED is off. The devices are in automatic mode after 

connection to the bus, and the respective manual operation buttons do 

not have a function.

Fig.7.2 Parameter window “Manual/Automatic Setting”

   7 .  parameter Setting DeSCription in the etS (continued)

7 .2 parameter window“manual/automatic Setting” (continued)

parameter “manual/automatic button”
The parameter defines if the switchover between the “manual 

operation” and “automatic operation” operating states is disabled or 

enabled using the manual/automatic button on the binary input.

Options:  Enable/Disable by object 

Enable

If the enable/disable by object is selected, the “En/Dis Man. /Auto” 

communication object appears. The object receiving telegram value “0” 

disable the manual/automatic button, and then the manual / automatic 

mode cannot be switched. If the object receiving telegram value “1” 

enable the manual/automatic button, and then the manual/automatic 

mode can be switched.
If the enable is selected, the manual/automatic button has been 

enabled.
parameter “manual to automatic method”
This parameter defines how long the binary input remains in the 

“manual operation” state after the “manual/automatic button” has been 

pressed.

Options:  By push button 

Automatically and by push button

If the by push button option is selected, the binary input will remain in 

“manual operation” until the manual/automatic button is pressed again.
If the automatically and by push button option is selected, the binary 

input will remain in “manual operation” until the manual/automatic 

button is pressed again or the parameterized Manual to automatic after 

[10…60000]*1s has timed out.

parameter “manual to automatic after [10 . . .60000]*1s”
The parameter appears when automatically and by push button is 

selected in the parameter manual to automatic method. It is used for 

setting the time for automatic reset from the “manual operation” to 

“automatic operation” state after the last push of a button.

Option:10……60000s

Parameter “Report on Man/Auto status change”
The parameter defines whether report on man/auto status change, and 

the current status can be sent to the bus.

Options:   Yes 

No

If the “yes” option is selected, the “Report Man/Auto Status” 

communication object appears. The object sends telegram value “1”, 

the current status for manual operation; the object sends telegram 

value “0”, the current status for automatic operation. When operation 

status changed, the object sends the current status telegram on the bus 

immediately.

7 .3 parameter window“enable/Disable manual operation”

Parameter window “Enable/Disable manual operation” can be shown 

in fig. 5.3. It is used to set whether the respective manual operation 

buttons do have a function in the manual mode.

Fig.7.3 Parameter window “Enable/Disable manual operation”

Summary of Contents for 0 026 93

Page 1: ...ointly adjustable Shutter 4 6 2 4 Communication object Switch 4 6 2 5 Communication object Switch Dimming 4 6 2 6 Communication object Value force output 5 6 2 7 Communication object Scene control 5 6 2 8 Communication object Switch sequence 6 6 2 9 Communication object Counter 6 6 2 10 Communication object Multiple operation 7 6 2 11 Communication object Shutter control 7 7 Parameter setting desc...

Page 2: ...tion via KNX bus 360mW Input Number 4 Permitted voltage range Un 0 265V AC DC Input current In Max 2mA Signal level for 0 signal 0 3V AC DC Signal level for 1 signal 9 265V AC DC KNX bus via bus connecting terminal Connections EIB KNX Via bus connection terminal Inputs Using screw terminals Cable cross section Multi core 0 2 2 5mm Single core 0 2 4 0mm Tightening torque Max 0 6 Nm Permitted cable ...

Page 3: ...nient to count the daily consumption Push button with multiple operation For triggering various functions depending on the frequency of the operation A long operation can also be detected and trigger a function Shutter control For movement lamella adjustment of a blind or a shutter via a one push button or two push buttons function Eight preset operating responses are possible in total Channel dis...

Page 4: ... UpDown This communication object is used to send a shutter moving command up or down to the bus Telegram value 0 move up 1 move down 2 Shutter stop X Y Shutter stop X Y 1bit C T 1 007 DPT_ Step This communication object is used to send a stop shutter moving command Telegram value 0 stop moving 1 stop moving Table 6 3 Communication object table Jointly adjustable Shutter 6 PARAMETERSANDCOMMUNICATI...

Page 5: ...128 127 1byte 0 255 1byte recall scene 1byte store scene 2byte 32768 32767 2byte 0 65535 2byte Float 3byte time of day 4byte 2147483648 2147483647 4byte 0 4294967 295 1 001 DPT_Switch 6 010 DPT_Value_1_Count 5 010 DPT_Value_1_Ucount 17 001 DPT_SceneControl 18 001 DPT_SceneControl 8 001 DPT_Value_2_Count 7 001 DPT_Value_2_Ucount 9 001 DPT_Value_Temp 10 001 DPT_TimeOfDay 13 001 DPT_Value_4_Count 12 ...

Page 6: ... in Fig 6 9 Including main counter and differential counter communication object both these communication objects will start count when the input pulse is generated with an operation The data width which has been selected for both counters can be set to same or different But the counting is independent of each other Fig 6 9 Communication object Counter No Function Object name Data type Flags DPT 1...

Page 7: ...on selected yes Once detected a long operation the object will send telegram value on the bus the telegram is set with the parameter value send object Tele Long operation Table 10 Communication object table Multiple operation 6 2 11 Communication object Shutter control The communication object Shutter Control will be shown in Fig 6 11 Fig 6 11 Communication object Shutter Control 6 PARAMETERSANDCO...

Page 8: ...rameter Manual Automatic button The parameter defines if the switchover between the manual operation and automatic operation operating states is disabled or enabled using the manual automatic button on the binary input Options Enable Disable by object Enable If the enable disable by object is selected the En Dis Man Auto communication object appears The object receiving telegram value 0 disable th...

Page 9: ...one button operation Fig 7 5 1 Parameter window Preset Channel A D separately adjustable working mode 7 ParametersettingdescriptionintheETS continued 7 5 Parameter window Preset Channel A D continued Fig 7 5 2 Parameter window Preset Channel A D Jointly adjustable working mode 7 5 1 Jointly adjustable working mode for binary input In the jointly adjustable working mode for binary input each jointl...

Page 10: ...5 2 1 Switch operating mode continued This parameter defines whether the input distinguishes between a short and long operation If yes is selected there is a delay after opening closing the contact to determine whether there is a short or long operation Only then is a possible reaction triggered The following diagram illustrates the function Input signal TL Possible reaction to the input signal Po...

Page 11: ...unce period As shown below Input signal TL Detected pulse edge TL TL Once a pulse edge has been detected at the input further edges are ignored for the duration of the debounce time TD The process of preventing debounce in the below chapters are the same with here TD is the effective time of a pulse edge input namely the period after a input signal is recognised as a operation 7 Parametersettingde...

Page 12: ...he parameter dimming functionality It is used to set if the object dimming X sends a brighter or darker telegram with long operation When the operation is over the object will send a stop dimming telegram Options Dimming BRIGHTER Dimming DARKER Dim BRIGHTER DARKER with start BRIGHTER Dim BRIGHTER DARKER with start DARKER If the option Dim BRIGHTER DARKER with start DARKER is selected the dim comma...

Page 13: ...ions Normally open Normally closed The parameters that are described in this chapter are based on normally open connect type as example the normally close connect type is just opposite Parameter Long operation after Base Factor 2 255 The parameter is visible if the option yes has been selected with the parameter distinction between long and short operation Here defines the period TL after which an...

Page 14: ...en the object value 1 will not send out again when long operation The objects Output group A F can be modified via the bus for the duration of the long operation Once the long operation has finished the object Store scene X sends the value 0 on the bus and the current object value can not be modified On the long operation If the object Store scene X receives the value 0 on the bus even the long op...

Page 15: ...ter No of objects The parameter set the number of communication objects has the same meaning the number of levels max 5 The communication objects level 1 to level 5 are enabled accordingly Options 2level 3level 4level 5level For example parameter 3level means there are 3 communication objects level 1 level 2 and level 3 The first operation modified the value of level 1 the second operation modifie...

Page 16: ...bouncing prevents unwanted multiple operation of the input e g due to bouncing of the contact Options 10ms 20ms 150ms Min operation The Min operation can be set in fig 5 8 Parameter Enable differential counter The parameter set whether enable the differential counter Options Yes No If this parameter is set to yes the parameter window fig 5 14 3 is displayed 7 ParametersettingdescriptionintheETS co...

Page 17: ...imit value 1 is preset for every data type to 0 The limit value 2 is preset which depend on the data width of main counter selected and the input field of limit value 2 can be freely edited 7 ParametersettingdescriptionintheETS continued 7 5 Parameter window Preset Channel A D continued 7 5 2 Separately adjustable working mode for binary input continued 7 5 2 6 Counter continued Parameter Send cou...

Page 18: ...es in detail 3 fold operation as an example the value send for toggle If the option 3 fold operation is selected there are three objects value appear and they are not independent meanwhile they send value according to a certain sequence 1 fold 2 fold 3 fold In order to state clear the following parameter Value on every operation set YES if operation count reach Max number of operations in a certai...

Page 19: ...apter are based on normally open connect type as example the normally closed connect type is just opposite 7 ParametersettingdescriptionintheETS continued 7 5 Parameter window Preset Channel A D continued 7 5 1 Jointly adjustable working mode for binary input continued 7 5 2 8 Shutter Control continued Parameter Operation functionality type This parameter sets the shutter operating functionality t...

Page 20: ... operation Options Move up Move down Parameter Reaction on operation It is visible if the shutter operation functionally type is 2 push button moving shutter 2 switch operation moving shutter and 2 pushbutton stepping It is defines the action when operation Different operation functionally type makes different operate action The former two operations functionally type is move up and down the last ...

Reviews: