Catalogue number(s): 0 026 93

KNX 4 channels binary input interface

   7 .  parameter Setting DeSCription in the etS (continued)

7 .3 parameter window“manual/automatic Setting” (continued)

parameter “Channel a . . .D manual button”
This parameter enables or disables the operation of the manual 

operation button. It is set separately for each channel.

Option:   Enable 

Disable

If the “enable” option is selected, the manual operation button is 

enabled. The first time the manual operation button is actuated, closing 

of the “external contact” is simulated, nothing happens when the button 

is released. The second time the manual operation button is actuated, 

opening of the “external contact” is simulated, nothing happens when 

the button is released.
If the “disable” option is selected, the manual operation button is 

disabled, and the manual operation buttons do not have a function. 

On disabled channels the respective channel LED will not react if the 

respective manualoperation button is pressed.

For safety-relevant systems such as for fault signals the button functions 

are inhibited using the disable option.

7 .4 parameter window“Channel leD”

Parameter window “Channel LED” can be shown in fig.5.4. It used to set 

channel LED indicate as a normal or inverted function for binary input in 

manual or automatic mode.

Fig.7.4 Parameter window “Channel LED”

parameter “Channel a . . .X leD”
This parameter is used to represent the LED display as a normal or 

inverted function. It is set separately for each channel.

Option:   Normal 

Inverted

If the Normal option is selected,represent the LED display as a normal 

function, then contact is closed(signal is present), LED is on; Contact is 

open (no signal), LED is off.
If the inverted option is selected,represent the LED display as a inverted 

function, then contact is closed(signal is present), LED is off; Contact is 

open (no signal), LED is on.

7 .5 parameter window“preset Channel a~D”

Parameter window “Preset Channel A~D” can be shown in fig. 5.5. 

Channel function of Binary input can select two ways of working. If 

the separately adjustable working way is selected, each channel can 

be set separately. If the jointly adjustable working way is selected, two 

channels can be set to work jointly, such as channel A and channel B 

jointly, channel C and channel D jointly. Each jointly adjustable can be 

set separately, which is used to set dimming and shutter functions. It is 

able to switch and dimming together with one button operation input, 

and it is also able to move and stop shutter with one button operation.

Fig.7.5(1)Parameter window “Preset Channel A~D”(separately adjustable working 

mode)

   7 .  parameter Setting DeSCription in the etS (continued)

7 .5 parameter window“preset Channel a~D” (continued)

Fig.7.5(2)Parameter window “Preset Channel A~D” (Jointly adjustable working 

mode)

7 .5 .1 jointly adjustable working mode for binary input

In the jointly adjustable working mode for binary input, each jointly 

adjustable can be set separately, and parameters and objects which 

are assigned to each jointly adjustable are the same. Using channel 

A/B jointly adjustable as an example described, the parameters can be 

shown in fig.5.5(2).
parameter“function Select X/Y”
This parameter set work ways of channel X/Y.

Options:  Separately adjustable 

Jointly adjustable (dimming, shutter)

If the “Jointly adjustable (dimming, shutter)” option is selected, channel 

X/Y for jointly adjustable work mode, in the follow parameters appear.
parameter “function X/Y”
The parameter set the functions of channel X/Y in the jointly adjustable, 

which is used to set dimming or shutter.

Option:  Dimming with two inputs with stop telegram 

Shutter with two inputs with stop telegram

The jointly adjustable function of channel X/Y can realize the dimming 

or the shutter via two objects. In automatic operation mode, channels 

input for 9~265V. In manual operation mode, channels input by manual 

operation buttons.
parameter “Channel assignment X/Y”
The parameter set the function assignment of channel X/Y in the jointly 

function for dimming.

Option:  Off, darker / on, brighter 

On, brighter / off, darker 

Toggle, darker / Toggle, brighter 

Toggle, darker / Toggle, brighter

If the “Off, darker / On, brighter” option is selected, represent input 

signal for “off, darker” when contact of channel X is closed, input signal 

for “stop darker” when contact of channel X is open. However, channel 

Y is opposite, Input signal for “on, brighter” when contact of channel Y is 

closed, input signal for “stop bright” when contact of channel Y is open. 

In the function assignment of channel X/Y other options are similar with 

the above option. The on/off formation is sent to the bus via the object 

“switch, X/Y”, the darker/brighter formation is sent to the bus via the 

object“ dimming, X/Y”.
Here setting the function assignment of channel X/Y in the jointly 

function for shutter.

Option:  MOVE Down/MOVE Up with stop 

MOVE Up/MOVE Down with stop

If the “MOVE Down/MOVE Up with stop” option is selected, the shutter 

move down when contact of channel X is closed, the shutter move up 

when contact of channel Y is closed. When the contact of channel X/Y is 

open, the shutter stops moving down/up.
Another option is similar with the above option. The shutter moves 

up/down via the object “Shutter move up/down, X/Y”. To stop shutter 

moving via the object “shutter stop, X/Y”.

Summary of Contents for 0 026 93

Page 1: ...ointly adjustable Shutter 4 6 2 4 Communication object Switch 4 6 2 5 Communication object Switch Dimming 4 6 2 6 Communication object Value force output 5 6 2 7 Communication object Scene control 5 6 2 8 Communication object Switch sequence 6 6 2 9 Communication object Counter 6 6 2 10 Communication object Multiple operation 7 6 2 11 Communication object Shutter control 7 7 Parameter setting desc...

Page 2: ...tion via KNX bus 360mW Input Number 4 Permitted voltage range Un 0 265V AC DC Input current In Max 2mA Signal level for 0 signal 0 3V AC DC Signal level for 1 signal 9 265V AC DC KNX bus via bus connecting terminal Connections EIB KNX Via bus connection terminal Inputs Using screw terminals Cable cross section Multi core 0 2 2 5mm Single core 0 2 4 0mm Tightening torque Max 0 6 Nm Permitted cable ...

Page 3: ...nient to count the daily consumption Push button with multiple operation For triggering various functions depending on the frequency of the operation A long operation can also be detected and trigger a function Shutter control For movement lamella adjustment of a blind or a shutter via a one push button or two push buttons function Eight preset operating responses are possible in total Channel dis...

Page 4: ... UpDown This communication object is used to send a shutter moving command up or down to the bus Telegram value 0 move up 1 move down 2 Shutter stop X Y Shutter stop X Y 1bit C T 1 007 DPT_ Step This communication object is used to send a stop shutter moving command Telegram value 0 stop moving 1 stop moving Table 6 3 Communication object table Jointly adjustable Shutter 6 PARAMETERSANDCOMMUNICATI...

Page 5: ...128 127 1byte 0 255 1byte recall scene 1byte store scene 2byte 32768 32767 2byte 0 65535 2byte Float 3byte time of day 4byte 2147483648 2147483647 4byte 0 4294967 295 1 001 DPT_Switch 6 010 DPT_Value_1_Count 5 010 DPT_Value_1_Ucount 17 001 DPT_SceneControl 18 001 DPT_SceneControl 8 001 DPT_Value_2_Count 7 001 DPT_Value_2_Ucount 9 001 DPT_Value_Temp 10 001 DPT_TimeOfDay 13 001 DPT_Value_4_Count 12 ...

Page 6: ... in Fig 6 9 Including main counter and differential counter communication object both these communication objects will start count when the input pulse is generated with an operation The data width which has been selected for both counters can be set to same or different But the counting is independent of each other Fig 6 9 Communication object Counter No Function Object name Data type Flags DPT 1...

Page 7: ...on selected yes Once detected a long operation the object will send telegram value on the bus the telegram is set with the parameter value send object Tele Long operation Table 10 Communication object table Multiple operation 6 2 11 Communication object Shutter control The communication object Shutter Control will be shown in Fig 6 11 Fig 6 11 Communication object Shutter Control 6 PARAMETERSANDCO...

Page 8: ...rameter Manual Automatic button The parameter defines if the switchover between the manual operation and automatic operation operating states is disabled or enabled using the manual automatic button on the binary input Options Enable Disable by object Enable If the enable disable by object is selected the En Dis Man Auto communication object appears The object receiving telegram value 0 disable th...

Page 9: ...one button operation Fig 7 5 1 Parameter window Preset Channel A D separately adjustable working mode 7 ParametersettingdescriptionintheETS continued 7 5 Parameter window Preset Channel A D continued Fig 7 5 2 Parameter window Preset Channel A D Jointly adjustable working mode 7 5 1 Jointly adjustable working mode for binary input In the jointly adjustable working mode for binary input each jointl...

Page 10: ...5 2 1 Switch operating mode continued This parameter defines whether the input distinguishes between a short and long operation If yes is selected there is a delay after opening closing the contact to determine whether there is a short or long operation Only then is a possible reaction triggered The following diagram illustrates the function Input signal TL Possible reaction to the input signal Po...

Page 11: ...unce period As shown below Input signal TL Detected pulse edge TL TL Once a pulse edge has been detected at the input further edges are ignored for the duration of the debounce time TD The process of preventing debounce in the below chapters are the same with here TD is the effective time of a pulse edge input namely the period after a input signal is recognised as a operation 7 Parametersettingde...

Page 12: ...he parameter dimming functionality It is used to set if the object dimming X sends a brighter or darker telegram with long operation When the operation is over the object will send a stop dimming telegram Options Dimming BRIGHTER Dimming DARKER Dim BRIGHTER DARKER with start BRIGHTER Dim BRIGHTER DARKER with start DARKER If the option Dim BRIGHTER DARKER with start DARKER is selected the dim comma...

Page 13: ...ions Normally open Normally closed The parameters that are described in this chapter are based on normally open connect type as example the normally close connect type is just opposite Parameter Long operation after Base Factor 2 255 The parameter is visible if the option yes has been selected with the parameter distinction between long and short operation Here defines the period TL after which an...

Page 14: ...en the object value 1 will not send out again when long operation The objects Output group A F can be modified via the bus for the duration of the long operation Once the long operation has finished the object Store scene X sends the value 0 on the bus and the current object value can not be modified On the long operation If the object Store scene X receives the value 0 on the bus even the long op...

Page 15: ...ter No of objects The parameter set the number of communication objects has the same meaning the number of levels max 5 The communication objects level 1 to level 5 are enabled accordingly Options 2level 3level 4level 5level For example parameter 3level means there are 3 communication objects level 1 level 2 and level 3 The first operation modified the value of level 1 the second operation modifie...

Page 16: ...bouncing prevents unwanted multiple operation of the input e g due to bouncing of the contact Options 10ms 20ms 150ms Min operation The Min operation can be set in fig 5 8 Parameter Enable differential counter The parameter set whether enable the differential counter Options Yes No If this parameter is set to yes the parameter window fig 5 14 3 is displayed 7 ParametersettingdescriptionintheETS co...

Page 17: ...imit value 1 is preset for every data type to 0 The limit value 2 is preset which depend on the data width of main counter selected and the input field of limit value 2 can be freely edited 7 ParametersettingdescriptionintheETS continued 7 5 Parameter window Preset Channel A D continued 7 5 2 Separately adjustable working mode for binary input continued 7 5 2 6 Counter continued Parameter Send cou...

Page 18: ...es in detail 3 fold operation as an example the value send for toggle If the option 3 fold operation is selected there are three objects value appear and they are not independent meanwhile they send value according to a certain sequence 1 fold 2 fold 3 fold In order to state clear the following parameter Value on every operation set YES if operation count reach Max number of operations in a certai...

Page 19: ...apter are based on normally open connect type as example the normally closed connect type is just opposite 7 ParametersettingdescriptionintheETS continued 7 5 Parameter window Preset Channel A D continued 7 5 1 Jointly adjustable working mode for binary input continued 7 5 2 8 Shutter Control continued Parameter Operation functionality type This parameter sets the shutter operating functionality t...

Page 20: ... operation Options Move up Move down Parameter Reaction on operation It is visible if the shutter operation functionally type is 2 push button moving shutter 2 switch operation moving shutter and 2 pushbutton stepping It is defines the action when operation Different operation functionally type makes different operate action The former two operations functionally type is move up and down the last ...

Reviews: