KNX modular dimmer 2 x 300 W

  

7.   COMMUNICATION OBJECTS

 

(continued)

7.3 Channel 1 and 2 parameters (continued)
7.3.5 "Load" parameter

This parameter is used to select loads.

"Load selection"
Automatic
 (by default): automatic load recognition.

Forced: if forced mode is chosen, it opens the possibility of choosing 

other options:

"Load commutation” (Load switching)
Trailing Edge
 (by default)

Leading Edge

"Load type"
Parameter which is used to select the load type:

• Incandescent-Halogen (by default)

• Transformer

• Compact fluorescent

• LED < 40 W

• LED < 75 W

"Maximum level %"
100
 (default value), this value can vary from 1 to 100

"Minimum level %"
10
 (default value), this value can vary from 1 to 100

Summary of Contents for 0 026 54

Page 1: ...he device 3 5 1 1 Description of push buttons 3 5 1 2 Description of LED flashing 3 5 2 Load teach phase 3 5 3 Manual mode 4 5 4 NFC settings 4 5 4 1 Channel configuration 5 5 4 2 Load settings 5 5 4...

Page 2: ...m2 or 2 x 1 5 mm2 BUS consumption 3 mA Table of loads which can be controlled per channel R trailing or leading mode L leading mode Dimmable Dimmable Dimmable LED 12 VAC 240 V Max 300W 200VA or 30 200...

Page 3: ...ntinued 5 1 2 Description of LED flashing Each push button press is associated with a flash and an LED colour The various flashing types and LEDs are detailed in the table below LED Colour Behaviour I...

Page 4: ...1 and 2 can then be switched ON OFF with a short press on the up and down buttons of each channel A long press on these buttons will brighten or dim the light 2 s 2 s 2 s ON OFF 2 s 2 1 To exit manua...

Page 5: ...300 VA max Compact fluorescent 100 W max LED 75 W max LED with noise reduction 40 W max Maximum level 20 to 100 Minimum level 2 to 85 5 4 3 Scene settings This is used to configure the different scene...

Page 6: ...trol unit receives a dimming command OFF time 2 s 1 s 1 H Time taken to go from 100 to 0 when the control unit receives an OFF command Level time 1 s 1 s 1 H Time taken to go from 0 to 100 when the co...

Page 7: ...Automatic by default automatic load recognition Forced if forced mode is chosen it opens the possibility of choosing other options Load commutation Load switching Trailing Edge by default Leading Edge...

Page 8: ...de leading or trailing mode etc 1 Check whether the load is dimmable 2 Check that there is not a mixture of load types The load does not react correctly to the dimming request Inappropriate setting 1...

Page 9: ...EDbulb MV 10W 806lm 2015 1 to 4 Leading mode LED with noise reduction 40 W OK Set the minimum light level if necessary The Dimmer without memory function is not recommended due to the lamp technology...

Page 10: ...5 1 to 8 Leading or trailing mode Transformer LED Not OK 1 to 5 bulbs Leading mode LED with noise reduction 40 W Set the minimum light level if necessary 6 to 8 bulbs Leading mode LED 75 W Set the min...

Page 11: ...and 100 If the transformer makes a buzzing noise switch to trailing mode 1 to 4 max LEGRAND TMDO 50 45 W FERRO Leading mode Transformer OK Set the minimum light level if necessary Dimming range can b...

Reviews: