background image

INSTALLATION REQUIREMENTS

4

This appliance must only be installed in Great Britain or Ireland.

1. This appliance is a natural gas appliance only and has been designed for use with the following applications:

a) 

Class I

- Conventional brick or stone chimney as used for a solid fuel fire with a cross sectional dimension of

225mm x 225mm (9” x 9”) or a lined flue with a minimum diameter of 175mm (7”), with the fireplace components
conforming to BS1251, or a builders opening a minimum of 560mm high and 335mm wide with a minimum depth
of 110mm to allow sufficient volume for debris collection. To obtain this depth it would not normally be necessary
to remove the chair brick. Any permanent flue restrictions or variable dampers are to be removed or locked in the
fully open position. The chimney should also be swept prior to installation.

b) 

Class II

- A double walled or insulated metal flue box built to the requirements of BS715 with an insulated flue

having a minimum diameter of 125mm (5”) and a minimum effective overall height of 3 metres (10’).

c) 

Pre-cast Flue

conforming to BS 1289 Part 1 (It may be necessary to use a surround with a deeper rebate

than usual to accommodate a flush fit with certain starter blocks. Check the appliance dimensions against
individual applications. Pre-cast flue block systems should comply with BS EN 1806 (clay/ceramic) or BS EN
1858 (concrete).  The flue area measurement is taken on the rectangular section above the gather block (length
x depth). The cross sectional area on post 1986 systems should not be less than 16500mm sq with a minimum
internal dimension 90mm. Gas operatives need to be aware that before 1986 the cross sectional area
specification was 13000mm sq with the minimum dimension of 63mm. In the case of the smaller flue the outlet
restrictor plate 

MUST

be fitted (see Fig. 2a).

2. A non-combustible hearth must be provided to comply with current building 
regulations. Care should be taken to prevent any damage being caused to 
surrounding soft furnishings or decoration, e.g. many embossed vinyl wall coverings 
may become discoloured if placed too close to the appliance.

3. A suitable proprietary fire surround with 100

0

c rating may be used with a minimum 

clearance from hearth to underside of shelf of 830mm, providing that the depth of shelf is 150mm or less.

4. Where the shelf depth is greater than 150mm, the minimum height clearance should be increased by 25mm
increments for each additional 12.5mm of shelf depth.

5. Minimum width between vertical sides of combustible surround should not be less than 800mm provided the
appliance is central to the surround and the surround legs do not exceed a 150mm profile.

6. If the 150mm profile is exceeded, the width of the surround (and the back panel) should be increased by 
25mm for each additional 12.5mm of profile depth.

FLUE FLOW TEST

A flue flow test (smoke test) is carried out to check the effectiveness of the flue and to ensure that there is no
leakage into another part of the premises (including any loft), or as appropriate other adjoining premises (this is
particularly important where a number of chimneys combine into a multiple stack).
The flue flow test should be carried out using a suitable smoke pellet which the pellet manufacturer claims to
generate 5m

3

of smoke in 30 seconds burn time.

These gas fires should have the flue flow test carried out with the appliance in position but not connected to the
gas supply so that the smoke test can be carried out with representative flue flow conditions.
A warm flue will be more effective than a cold flue. If the flue is reluctant to draw, which can be initially assessed
by lighting a smoke match at the intended position of the appliance flue connection, introduce some heat into the
flue for a minimum of 10 minutes using a blow torch or other means.
Other factors, such as weather conditions and a combination of materials used to construct the flue can all
influence the flue draught. The pre-heating process may require as much as half an hour before the flue behaves
satisfactory as a blow torch does not represent the volume of heat consistent with the normal appliance
operation. A Flue Flow Test should be checked as follows:

1. Carry out those visual checks as indicated previously, and continue only if satisfactory.
2. Establish that an adequate air supply is available for the combustion of the appliance
3. Close all doors and windows in the room that the appliance is to be installed.
4. Light a smoke pellet at the intended position for the appliance. Place the inset fire case into position.
5. The test is satisfactory if: - there is no significant escape of smoke from the appliance position.

- there is no seepage of smoke over the length of the flue.
- smoke is discharged only from the correct terminal.

VENTILATION

No special ventilation bricks or vents are required in the room containing the appliance, providing that normal
adventitious room ventilation exists. The installer must determine this by carrying out a spillage test.

SPILLAGE TEST

To check for satisfactory clearance of products of combustion, close all doors and windows and leave the fire
burning for five minutes. Insert a lit smoke match on a vertical plane 50mm down, 50mm inside the canopy
opening. All the smoke must be drawn into the flue. If spillage occurs, allow a further ten minutes and repeat the
test. Should spillage still occur turn the appliance off and seek expert advice.
To continue the test: If an extractor fan is situated in the room the test should be repeated with the fan running. If
there is a connecting room with an extractor fan the test should be repeated with all the doors to that room open
and the extractor fan running.

Fig. 2a

Restrictor

Summary of Contents for Spirit Superslim

Page 1: ...and then should be handed to the end user when the installation is complete This is an official requirement and is the responsibility of the fitter of this appliance Having installed the appliance the installer should take the necessary steps to ensure that the user fully understands how to operate the appliance and is also made aware of the fire s basic cleaning and maintenance requirements ...

Page 2: ...missioning 6 Technical Data 7 Replacement Parts 7 Trouble Shooting GAS SAFE Engineer Only 8 User Instructions 9 Cleaning and Maintenance 10 Ignition System Wiring Diagram 11 Fire Front Specifications 11 Coal Layout Instructions 12 Pebble Layout Instructions 14 Guarantee 16 Trouble Shooting User 16 CONTENTS 2 ...

Page 3: ...open position The chimney flue must always generate a positive up draught to ensure safe operation The installer must then establish that all the products of combustion are entering the flue within five minutes of lighting from cold This can be verified by traversing the canopy with a lighted smoke match see Spillage Test page 4 An isolation valve must be fitted adjacent to the appliance When clos...

Page 4: ...e increased by 25mm for each additional 12 5mm of profile depth FLUE FLOW TEST A flue flow test smoke test is carried out to check the effectiveness of the flue and to ensure that there is no leakage into another part of the premises including any loft or as appropriate other adjoining premises this is particularly important where a number of chimneys combine into a multiple stack The flue flow te...

Page 5: ...o the box two on the front leg and two at the rear of the tray Remove the burner tray and place to one side Fig 3 6 When the burner tray has been removed decide which side of the appliance the gas supply will be entering the radiant box and remove the relevant blanking plate left or right hand side The gas supply should be concealed as much as possible 7 With the radiant box placed in the opening ...

Page 6: ...arry out a gas soundness test 1 Unscrew the pressure test point sealing screw Fig 7 and fit a manometer Consult the user instructions page 9 Ignite the appliance and turn to the high position 2 Take a pressure reading and consult the technical data page 7 to establish the correct working pressure 3 Once the pressure has been checked and verified turn off the appliance Consult the ceramic component...

Page 7: ...he consumer can do so provided that the Ceramic Component Layout Instructions pages 12 15 are adhered to Only genuine Legend replacement parts should be used Order Ref SSFC02 SSCM03 2 Oxygen Depletion Sensing Pilot In the unlikely event of a pilot failure the pilot assembly should only be replaced by a GAS SAFE Registered Engineer The user must not carry out this work Order Ref LEG01 3 Control Tap...

Page 8: ...elay the coal set as per Ceramic Component Layout Instructions pages 12 15 5 The fire makes a roaring noise when lit Check That the front coal is seated correctly and the pilot hole is positioned correctly over the pilot assembly IF ANY PART OF THE PILOT ASSEMBLY IS SUSPECTED AS BEING FAULTY THE COMPONENT MUST BE REPLACED 6 The flames appear blue after the fire has fully warmed up The coals cerami...

Page 9: ...ted back up to the minimum setting 6 To switch off the appliance completely simply lift the lever fully to the top position Note The pilot assembly fitted to this appliance has an oxygen depletion sensor built in to monitor the room for products of combustion If the sensor should operate and switches the appliance off re ignite the appliance following the procedure above Should the appliance repea...

Page 10: ...mponents as they will break if handled incorrectly Do not use a vacuum cleaner to clean the ceramics 2 Radiant Box Ceramic Liners Use only a soft brush to remove any soot deposits from the ceramic liners during cleaning as this is the only method that can be used to remove deposits The ceramic liners are very delicate and should be treated accordingly 3 Brass Trims and Frets The brass trim and fre...

Page 11: ...pliance has a naked flame and as with all heating appliances a fireguard should be used for the protection of children the elderly and infirm Fireguards should conform to BS 6539 1984 Fireguards for use with solid fuel appliances This fire is not fitted with an integral guard In normal use consideration may be given to the use of a fireguard confirming to BS 6539 such that the approach to the nake...

Page 12: ...ng sure that the back edge is pushed up against the front of the burner strip Fig 13 CAUTION The coals are extremely fragile and must be handled accordingly Gloves should be worn and any inhalation of dust should be avoided Never put additional coals on the fire Never use coals other than those originally supplied or genuine Legend Spare Parts Fig 12 Fig 14 Fig 15 Fig 13 Burner Strip Fuel Bed 4 Lo...

Page 13: ... shown in order to achieve the desired flame picture It may be necessary to remove some or all of the coals to clean them at some time Cleaning must only be done using a soft brush Ceramic touch up dye is available from Legend Fires 5 Finally check that all the coal pieces are nested together correctly Fig 16 ...

Page 14: ... sure that the back edge is pushed up against the front of the burner strip Fig 18 CAUTION The pebbles are extremely fragile and must be handled accordingly Gloves should be worn and any inhalation of dust should be avoided Never put additional pebbles on the fire Never use pebbles other than those originally supplied or genuine Legend Spare Parts Fig 17 Fig 19 Fig 20 Fig 18 Burner Strip Fuel Bed ...

Page 15: ... shown in order to achieve the desired flame picture It may be necessary to remove some or all of the pebbles to clean them at some time Cleaning must only be done using a soft brush Ceramic touch up dye is available from Legend Fires 5 Finally check that all the pebble pieces are nested together correctly Fig 21 ...

Page 16: ...oose coals and the front coal and thoroughly clean any debris in and around the pilot area If the fire will still not light contact your installer 2 The flames appear blue excessive soot deposits The ceramic components including the coal need relaying pages 12 15 Too much or too little room ventilation Seek professional advice 3 Roaring noise coming from the pilot The front coal is not seated corr...

Reviews: