Commissioning
Control Terminal Strip for 15HP (11 kW) and Greater Drives:
6 25 4 11 13A13B 13C
TXA
5
1 2
14 30 2
AOUT
DIGOUT
2k … 10k
+10 V
+12 V
AIN
AIN
COM
COM
ALsw
17
16
TXB
13D
13D
13D
25
2
4 … 20 mA
5
2
0 … 10 V
1 2 4 13A 13B 13C
+12 VDC - 0 %
. . .
+30 VDC + 0 %
ALsw
+15V
1 2 4 13A 13B 13C
ALsw
COM
4.5 lb-in
(0.5 Nm)
0.25 in (6 mm)
AWG 26…16
(<1mm²)
The digital inputs can be configured for active-high or active-low by setting the Assertion Level
Switch (ALsw) and P120. If wiring to the drive inputs with dry contacts or with PNP solid state
switches, set the switch and P120 to “High” (+). If using NPN devices for inputs, set both to
“Low” (-). Active-high (+) is the default setting.
HIGH = +12 … +30 V
LOW = 0 … +3 V
Note
An
F.AL
fault will occur if the Assertion Level switch (ALsw) position does not match
the parameter P120 setting and P100 or any of the digital inputs (P121...P123) is set
to a value other than 0.