22
Commissioning
4.5
Parameter menu
4.5.1
Basic Setup Parameters
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
P100
Start Control
Source
0
0 Local Keypad
Use RUN button on front of drive to
start
1 Terminal Strip
Use start/stop circuit wired into the
terminal strip. See Section 3.2.3
2 Remote Keypad Only
Use RUN button on optional Remote
Keypad to start
3 Network Only
• Start command must come from
network (Modbus, CANopen, etc)
• Requires optional communication
module (refer to the network
module documentation).
• Must also set one of the TB-13
inputs to 9 (Network Enable); see
P121...P123
4 Terminal Strip or Local
Keypad
Allows start control to be switched
between terminal strip and local
keypad using one of the TB-13
inputs. See note below.
5 Terminal Strip or Remote
Keypad
Allows start control to be switched
between terminal strip and optional
remote keypad using one of the TB-
13 inputs. See note below.
6 CTRL Button Select
Allows start control to be switched
between terminal strip and local
keypad using the CTRL button.
NOTE:
P100 Selection 6 is applicable
to 15 HP (11kW) and higher models
only.
WARNING!
P100 = 0 disables TB-1 as a STOP input! STOP circuitry may be
disabled if parameters are reset back to defaults (see P199)
Note
• P100 = 4, 5: To switch between control sources, one of the TB-13
inputs (P121...P123) must be set to 08 (Control Select);
TB-13x OPEN (or not configured): Terminal strip control
TB-13x CLOSED: Local (P100 = 4) or Remote (P100 = 5) keypad
• P100 = 0, 1, 4: Network can take control if P121...P123 = 9 and the
corresponding TB-13x input is CLOSED.
• The STOP button on the front of the drive is always active except in
JOG mode.
•
An
F.AL
fault will occur if the Assertion Level switch (ALsw)
position does not match the P120 setting and P100 is set to a
value other than 0.