Wiring

 CAUTION

Do not apply power to the unit until all secondary wiring is complete, and dip-

switches have been set.

All applications

The 8310-2420 comes with the relay module pre-wired to a labeled set of two terminal strips. A complete wiring diagram is 

adhered to the inside of the door to provide a layout of the wiring as a reference when wiring the field devices to the kit.
There are two terminal strips that mirror the locations on the relay module. The left strip is used for power to the relay 

module, the PUSH TO OPEN and PUSH TO LOCK buttons, the door position switch, and the Wet trigger. The right strip is for 

the outputs to drive the strike (Relay 1), door operator (Relay 2), electronic board LEDs (Relay3), and to provide VDC power 

for the door strike.
Once all field devices are wired to the 8310-2420, then AC power can be wired in.

 

L

IMPORTANT: Confirm the electrical panels breaker you are going to be using is currently off. Do not wire the 

primary terminals of the transformer until the secondary terminals are connected first.

The supplied transformer will have its secondary terminals wired to the terminals (red wires from the transformer) on the 

top of the left terminal strip marked as “AC”. Next, wire the primary terminals (black wires from the transformer) to the AC 

feed to be used. Confirm your connections and apply power by turning on the electrical panel breaker.

Actuator wiring

 

 

ACTIV

E

NC

CO

M

NO

PWR

 A

C/

D

C

ID

LE

 C

O

L

ENABLE

1   2   3

ON DP

1   2   3

ON DP

1   2   3

ON DP

-REM  +

-PBTN  +

EN

RF/T

X -

PWR

 +

Switch mounting

holes (x2)

“Push to Open” switch

Diffuser Ring

Mounting box

Box mounting

screw locations

Circuit board

mount (x2)

Power and

relay terminal

strip

Enable Dipswitch

Idle Col Dipswitch

Active Dipswitch

Wire Access

Hole (route

wires thru

this hole)

Wire to

Outside

"Push to Open"

terminals in

the cabinet

(via wire

access hole)

LED control

terminals in

cabinet

(via wire

access hole)

RED

GREEN

BLUE

Connected

to 24V DC

from the +/-

VDC terminals

in the cabinet

(via wire

access hole)

REM/LOC

RELA

Y

SPEAKER

Outside “Push to Open” actuator wiring diagram (typical)

Summary of Contents for 8310-2420

Page 1: ...for Door to Close vinyl decal 1 9 Door locked when red unlocked when green black vinyl sign 1 10 Door occupied when red vacant when green black vinyl sign 1 11 E strike with 3 faceplates and hardware...

Page 2: ...B2 Power 50 VA DPS Switch Descriptions 8310 2420 Series Power max 3 0 W Electrical configuration SPDT Suggested Wiring 22AWG Gap distance max 0 75 Operation at a glance When the exterior PUSH TO OPEN...

Page 3: ...onic board in place 1e Place the diffuser insert inside the flush enclosure making sure the mounting screw holes on the diffuser insert and the flush enclosure align For Push to Open switches a Use th...

Page 4: ...Safe mode when Mode Selector is pointing to FS Fail Lock mode when Mode Selector is pointing to Fail Lock Set Screw Mode Selector Mode Selector Set Screw L Note The products are intended to be instal...

Page 5: ...r The transformer should only be installed OUTSIDE of the Power Supply Cabinet per all National Electric Code NEC NFPA 70 requirements along with local code requirements and it should be kept in close...

Page 6: ...ently off Do not wire the primary terminals of the transformer until the secondary terminals are connected first The supplied transformer will have its secondary terminals wired to the terminals red w...

Page 7: ...ls in cabinet via wire access hole RED GREEN BLUE Connected to 24V DC from the VDC terminals in the cabinet via wire access hole REM LOC RELAY SPEAKER Wired to the Inside Push to Open terminals in the...

Page 8: ...0 50 seconds The second option d 1 flashing will be how long to wait before activating relay 2 0 15 seconds The third option H 2 flashing will be how long relay 2 will be activated for 0 50 seconds T...

Page 9: ...2 3 ON DP RED GREEN BLUE REM LOC RELAY SPEAKER See the diagrams below for the dip switch functionalities Enable Dip Switch Bank Idle COL Dip Switch Bank Switch number Description Switch number Descrip...

Page 10: ...K THIS DOOR WAIT FOR DOOR TO CLOSE Place sign on the door inside the restroom at eye level INSIDE THE RESTROOM POWER SUPPLY 6 12 24 VDC SMP3 24V OPEN CLSD CLSD OPEN SW1 SW2 6V OPEN OPEN 12V SW1 SW2 AC...

Page 11: ...shown connecting the Push to Open switch to the Push to Open terminals Com Rem PBTN N O Pwr AC DC Com Rem PBTN N O Pwr AC DC IMPORTANT Ensure wiring polarity is consistent from Relay 3 to each remote...

Page 12: ...osing the door or after pushing Push to Lock Logic Module not in Mode 7 Change Logic Module to Mode 7 and ensure all mode 7 settings are set as shown in the instructions No power to the strike Ensure...

Page 13: ...he solenoid releases This can be caused by too much stack pressure on the door pressing on the strike Electric Strike itself is set to Fail Secure rather than Fail Safe Follow the electric strike inst...

Page 14: ...is latching then the door may not fully latch If this occurs the source of the pressure force needs to be removed so that the door can fully close This can be caused by too much stack pressure preven...

Page 15: ...inals Take a jumper wire and touch the screw heads of the PBTN and terminals the actuators wires are hooked up to If the unit acts as if the actuator was actually pushed then either the actuator was w...

Page 16: ...ion DPS switch not closing contact Wiring issue Verify wiring is correct to Power Supply Relay Cabinet and DPS wires fully connected Incorrect mounting Mounting gap should be no more than 3 4 between...

Page 17: ...7 Cabinet base template 9 8 6...

Page 18: ......

Page 19: ......

Page 20: ......