background image

Auto Operator Wiring

Auto operator

COM

NO

4630/4640 Series Electric Auto-

Equalizers

Terminals 17 or 19

Terminals 16 or 18

7900 Series Pneumatic Auto-

Equalizers

Terminal 10

Terminal 8 (for Door A) or 

Terminal 6 (for Door B)

9100 Series Benchmark

Either “MAIN ACT” terminal

Either “MAIN ACT” terminal

2800/9500 Series Senior Swing

P6 or P7 cable, yellow wire

P6 or P7 cable, gray wire

Troubleshooting

Power supply/Relay cabinet

Scenario

Cause

Solution

No LEDs (Red or Green) 

on in Power Supply/Relay 

Cabinet

120V not supplied to transformer

Verify 120V connection to black wires (Primary) on 

transformer.

Improper wiring to transformer

Verify 120V connection to black wires (Primary) on 

transformer.

Incorrect voltage from transformer

Verify a minimum of 24VAC output from red wires 

(Secondary). Typical Output ~27VAC.

Logic Module Display 

won’t turn on, but Power 

Supply LEDs (Red & 

Green) on

Improper wiring from transformer to 

cabinet

Verify red transformer wires are wired to AC inputs 

on power supply (in cabinet).

Power wires disconnected

Verify the red and white wires are connected to 

Logic Module power input.
Verify red and white wires are connected to power 

board.

Power supply DIP switches set 

improperly

Verify DIP switches are set to 24V.

E-strike (Fail Safe mode)

Scenario

Cause

Solution

Electric strike 

won’t lock after 

closing the door 

or after pushing 

“Push to Lock”

Logic Module not in Mode 7

Change Logic Module to Mode 7 and ensure all mode 7 settings are 

set as shown in the instructions

No power to the strike

Ensure proper wiring from Door Strike terminals to  Electric Strike 

wiring harness (female).
Check if voltage is present across Door Strike terminals in the cabinet 

after pushing the button. If voltage is present, ensure all wires to the 

electric strike harness are fully connected and that the harness is 

fully seated/connected to the electric strike connector.
If voltage is not present across Door Strike terminals, ensure wires 

from the Logic Module are fully connected to the Door Strike 

terminals. If the wires are not connected, then they need to be 

connected. The Logic Module’s blue wire should go to the upper (+) 

terminal, and the Logic Module’s white wire should go to the lower 

(-) terminal.
If wires going from the Logic Module to the Door Strike terminals 

have not come loose/disconnected at either end, then check to 

ensure that the LED display on the Logic Module is lit up as ‘7’. If the 

module is set to ‘7’, then ensure all mode 7 settings are set as shown 

in the instructions.
If the LED Display is not on, then check the power troubleshooting 

section as either the module is bad or the module is not being 

powered up.
If the LED Display is not set to ‘7’, press the far left “MENU” button 

on the Logic Module and use the “UP” or “DOWN” buttons to scroll 

to mode ‘7’. Ensure all mode 7 settings are set as shown in the 

instructions.

Summary of Contents for 8310-2420

Page 1: ...for Door to Close vinyl decal 1 9 Door locked when red unlocked when green black vinyl sign 1 10 Door occupied when red vacant when green black vinyl sign 1 11 E strike with 3 faceplates and hardware...

Page 2: ...B2 Power 50 VA DPS Switch Descriptions 8310 2420 Series Power max 3 0 W Electrical configuration SPDT Suggested Wiring 22AWG Gap distance max 0 75 Operation at a glance When the exterior PUSH TO OPEN...

Page 3: ...onic board in place 1e Place the diffuser insert inside the flush enclosure making sure the mounting screw holes on the diffuser insert and the flush enclosure align For Push to Open switches a Use th...

Page 4: ...Safe mode when Mode Selector is pointing to FS Fail Lock mode when Mode Selector is pointing to Fail Lock Set Screw Mode Selector Mode Selector Set Screw L Note The products are intended to be instal...

Page 5: ...r The transformer should only be installed OUTSIDE of the Power Supply Cabinet per all National Electric Code NEC NFPA 70 requirements along with local code requirements and it should be kept in close...

Page 6: ...ently off Do not wire the primary terminals of the transformer until the secondary terminals are connected first The supplied transformer will have its secondary terminals wired to the terminals red w...

Page 7: ...ls in cabinet via wire access hole RED GREEN BLUE Connected to 24V DC from the VDC terminals in the cabinet via wire access hole REM LOC RELAY SPEAKER Wired to the Inside Push to Open terminals in the...

Page 8: ...0 50 seconds The second option d 1 flashing will be how long to wait before activating relay 2 0 15 seconds The third option H 2 flashing will be how long relay 2 will be activated for 0 50 seconds T...

Page 9: ...2 3 ON DP RED GREEN BLUE REM LOC RELAY SPEAKER See the diagrams below for the dip switch functionalities Enable Dip Switch Bank Idle COL Dip Switch Bank Switch number Description Switch number Descrip...

Page 10: ...K THIS DOOR WAIT FOR DOOR TO CLOSE Place sign on the door inside the restroom at eye level INSIDE THE RESTROOM POWER SUPPLY 6 12 24 VDC SMP3 24V OPEN CLSD CLSD OPEN SW1 SW2 6V OPEN OPEN 12V SW1 SW2 AC...

Page 11: ...shown connecting the Push to Open switch to the Push to Open terminals Com Rem PBTN N O Pwr AC DC Com Rem PBTN N O Pwr AC DC IMPORTANT Ensure wiring polarity is consistent from Relay 3 to each remote...

Page 12: ...osing the door or after pushing Push to Lock Logic Module not in Mode 7 Change Logic Module to Mode 7 and ensure all mode 7 settings are set as shown in the instructions No power to the strike Ensure...

Page 13: ...he solenoid releases This can be caused by too much stack pressure on the door pressing on the strike Electric Strike itself is set to Fail Secure rather than Fail Safe Follow the electric strike inst...

Page 14: ...is latching then the door may not fully latch If this occurs the source of the pressure force needs to be removed so that the door can fully close This can be caused by too much stack pressure preven...

Page 15: ...inals Take a jumper wire and touch the screw heads of the PBTN and terminals the actuators wires are hooked up to If the unit acts as if the actuator was actually pushed then either the actuator was w...

Page 16: ...ion DPS switch not closing contact Wiring issue Verify wiring is correct to Power Supply Relay Cabinet and DPS wires fully connected Incorrect mounting Mounting gap should be no more than 3 4 between...

Page 17: ...7 Cabinet base template 9 8 6...

Page 18: ......

Page 19: ......

Page 20: ......

Reviews: