Operating Instructions
72
Part No. 70476501ENR7
Fault Conditions
2 Flashes
Flame Without Call For
Heat
3 Flashes
Ignition Lockout
4 Flashes (70458701 only)
Manual Reset Error
Fault Conditions
Steady On
Internal Control Failure
NOTE: The LED will flash on for 1/4 second, then off
for 1/4 second during a fault condition. The pause
between fault codes is 3 seconds.
Internal Control Failure
If the control detects an error in its software or hardware, all
outputs are turned off and the red LED displays a steady ON
condition. If this condition persists after an attempt to restart,
then the control must be replaced.
Troubleshooting
Troubleshooting Guide
Symptom
Probable Cause
Control in Lockout Mode (70458701 Control Only)
Manual reset of the control is needed. Reset by pushing red
lockout button or use front end control.
Control does not start, green LED is off
1. 24 VAC present between 24V and ground on 70458701
only. If not, see machine schematic.
2. 24 VAC present between TH and ground. If not, see machine
schematic.
Thermostat on, no spark or valve
1. Cable connects to control and electrode. Voltage present at
gas valve.
2. Bad control. Check red LED for steady on or flashing codes.
Valve on, no spark during TFI
1. Shorted electrode.
2. Spark gap not correct. Set to .094-.156 inch.
3. High voltage cable is faulty or has a poor connection.
4. Control failure.
Spark on, no flame
1. Is gas on?
2. 24 VAC at gas valve.
3. Bad control. Check voltage between gas valve terminal MV
and GND on control.