Through flow coolers
16/03/2018/ YAFE0004
23
10.1 Refrigerant and filling quantity
The device contains fluorinated greenhouse gases.
Unit
DLK 10
DLK 25
DLK45
DLK 45 LiBus
Refrigerant
---
R-134a
R-404A
R-404A
maximum filling quantity
kg
0.075
0.3
1.1
GWP
(100a)
*
---
1430
3922
3922
CO
2
equivalent
t
0.1
1.2
4.3
Global Warming Potential (GWP),
Comparison CO
2
= 1,0
* Time span 100 years - according to IPCC IV
10.2 Fuses
two fuses per device
F1 and F2
DLK 10
DLK 25
DLK 45
DLK 45 LiBus
230 V; 50/60 Hz
T 6,3 A
5 x 20 mm
(EEF 006)
-----
-----
-----
230 V; 50 Hz
-----
T 8 A
5 x 20 mm
(EEF 028)
T 16 A
6.3 x 32 mm
(EES 013)
T 16 A
6.3 x 32 mm
(EES 013)
230 V; 60 Hz
-----
T 8 A
5 x 20 mm
(EEF 028)
-----
T 16 A
6.3 x 32 mm
(EES 013)
208-220 V; 60 Hz
-----
-----
-----
T 16 A
6.3 x 32 mm
(EES 013)
208-230 V; 60 Hz
-----
-----
T 16 A
6.3 x 32 mm
(EES 013)
-----
100 V; 50 Hz /
115 V; 60 Hz
T 10 A
5 x 20 mm
(EEF 026)
T 16 A
5 x 20 mm
(EEF 024)
-----
-----
We reserve the right to make technical alterations!