Through flow coolers
22
16/03/2018/ YAFE0004
10
Technical data
The figures have been determined according to DIN 12876
DLK 10
DLK 25
DLK 45
DLK 45 LiBus
Operating temperature range
°C
-15
– 150
-30
– 150
-40
– 150
-40
– 150
Ambient temperature range
°C
5
– 40
Gross cooling capacity
(to DIN 12876 T2)
20 °C
0 °C
-10 °C
-20 °C
-30 °C
-40 °C
kW
kW
kW
kW
kW
kW
0.25
0.20
0.10
------
------
------
0.33
0.28
0.25
0.22
0.20
------
1.10
0.95
0.85
0.75
0.55
0.30
1.10
0.95
0.85
0.75
0.55
0.30
Heat exchanger connections
for heat carrier
M16 x 1, olives diameter 13 mm
Special features
control connection
for mains supply
Proportional-
cooling with
C/K-P or E 300
Proportional-cooling
with Proline heating
thermostat
Heat exchanger
coaxial
plate-heat exchanger
Overall dimensions
W x D x H
mm
200 x 400 x
320
290 x 540 x
330
470 x 560 x
430
470 x 560 x 430
Weight
kg
17
33
63
63
Protection class
Protection class 1 according to DIN EN 61140 VDE 0140-1
Power consumption
kW
0.2
0.5
0.9
0.9
Mains connection
DLK 10
DLK 25
DLK 45
DLK 45 LiBus
230 V; 50/60 Hz
X
-----
-----
-----
230 V; 50 Hz
-----
X
X
X
230 V; 60 Hz
-----
X
-----
X
208-220 V; 60 Hz
-----
-----
-----
X
208-230 V; 60 Hz
-----
-----
X
-----
100 V; 50 Hz / 115 V; 60 Hz
X
X
-----
-----