Calibrate Touch Pad Control Switch
The touch
pad can be calibrated for the specific pool it is installed on. This calibration will teach the touch
pad what the electrical current consumption is (for retrofit models) and what the transit operation time
will be in normal operation. The touch
pad utilizes this information to determine over currents and cycle
calculations.
1. Access the service menu using the service passcode
.
(5991)
2. Press the Service button. The display will alternate between showing the “service con
tact
information” and “Press Select (5) for Menu”.
3. Press Select (5).
4. Press the down arrow (8) until “Calibrate Pool” is visible. Press the Select (5) button to
select this option.
5. Operate the cover until it is in its fully uncovered position.
6. Press Select (5) to confirm that the pool is completely uncovered.
7. Operate the cover until it is in its fully covered position.
8. Press Select (5) to confirm that the pool is completely covered.
9. Operate the cover until it is in its fully uncovered position.
10. Press Select (5) to confirm that the pool is completely uncovered.
11. The display will show the amp draw and time of operation for both covering and
uncovering the pool. Press Select (5) to accept these measurements.
Adjust Current Limits:
The
t
ouch
pad
r
etrofit model supports electronic current limiting. The default current settings are 7.5
Amps. The system will
actively monitor operation of the cover and stop the system if current exceed
150% of the above value. To adjust these
settings do the following
:
1. Access the service menu using the service passcode (5991)
2. Press the Service button. The display will alternate between showing the “service contact infor
mation"
and
"Press Select (5) for Menu".
3. Press Select (5).
4. Press the down arrow (8) until “Current Limits” is shown. Press the Select (5) button to select
this option.
5. The display will show the average amp readings while opening the cover and the current limit
setting
for
opening the cover.
6. To change the average amp reading, press the up arrow (2) or down arrow (8) buttons. Press
Select (5)
to
advance the curser to the limit setting.
7. To adjust the limit setting, press the up arrow (2) or the down arrow (8) buttons. Press Select (5)
to save
the
new settings.
8. Make the same adjustments for the settings for closing the cover.
9. Press Select (5) to save the new amp and torque settings and return to the service screen.
Press the service button at any time to cancel the process