ICS-TOUCH Instruction Manual
CEB00XXX-53-000
Page 7 of 43
Issue 4 19 January 2021
The ICS-6-SP is connected to the ICS-TOUCH panel by an RS232 serial data link. A 24V power supply
is also required. The ICS-TOUCH acts as a status display for the ICS-6-SP and allows the user to arm
and disarm the controller.
Lasermet provides a full range of laser interlock equipment including control systems, interlock
switches, illuminated warning signs, laser shutters, door locks, external power supplies etc. which
can be connected to provide a complete laser interlock system. Full support, design and installation
is available from Lasermet, please contact us for any queries. Contact details are given at the end of
this manual.
4
Summary of Evaluation of Compliance to EN ISO 13849-1:2015
To achieve a complete system performance level ‘e’ the system must be wired as described in this
manual using suitably rated door sensors and measures taken to minimise the effects of common
cause failures in the sensors and wiring which may be connected to the unit.
Achieved Characteristics:
Architecture
Category 4
Performance Level (PL)
PL = e
PFH [1/h]
2.47 x 10
-8
(based on MTTFd being ‘capped’ at 100 years)
MTTFd
381 years
Mission Time
20 years
Diagnostic Coverage (DC)
99% (HIGH)