background image

EPL-LED-150W-RT-XEMG-SP0009

Larson Electronics, LLC

 

  Phone: (800) 369-6671 

 Fax: (903) 498-3364 

 www.larsonelectronics.com 

2

 of 

3

 

For supply connections, use wire rated for at least 110°C 

WIRING 
Standard pigtail(flying leads) wiring 

We strongly encourage a licensed electrician install this product

, in all locations especially in outdoor areas 

where weatherproofing may be required. Universal voltage driver permits operation at 100V  -  277V AC, 50 or 60Hz 

except those factory ordered with low voltage 11V to 25V AC/DC. 

Warning: 

Check product label for correct input voltage!

 

Attach supply line wires to the appropriate light fixture wires as shown 

in the diagram 

 

Secure each pair of wires according to the diagram. Utilize a junction box or 

similar  device  and  take  precautionary  steps  for  weatherproofing  all 

connections if installed in a location where water may come in contact with the 

unit. Ensure the unit is properly grounded and that wiring is done according to 

all local and national electrical/building codes. 

WARNING:

 

The  emergency  battery  backup  enclosure  and  plug  are  NOT  rated  for  Hazardous 

Areas.  The  Emergency  Battery  Backup  enclosure 

AND

  Cord  Cap 

MUST

  remain 

OUTSIDE  the 

Hazardous Area during use! 

Keep emergency battery backup ballast box closed at all 
times during operation. Follow all applicable local, state, and 
National Electrical Code for the hazardous area! 

WARNING:

 CHECK NAMEPLATE 

FOR PROPER VOLTAGE. DAMAGE 
FROM IMPROPER VOLTAGE WILL 
VOID WARRANTY. 

MAINTENANCE 

Caution: 

To avoid personal injury, disconnect power to the light and allow the unit to cool down before 

performing maintenance. 

Warning: 

No user serviceable parts inside of fixture. Risk of electric shock. Removal of the lens will void 

the warranty. 

1.

Perform visual, mechanical and electrical inspections on a regular basis. We recommend routine

checks to be made on a yearly basis. Frequency of use and environment should determine this.  It is

recommended to follow an Electrical Preventive Maintenance Program as described in NFPA 70B:

Recommended practice for Electrical Equipment.

2.

The lens should be cleaned periodically as needed to ensure continued photometric performance.

Clean the lens with a damp, non-abrasive, lint-free cloth. If not sufficient, use mild soap or a liquid

cleaner.

3.

Inspect the cooling fins on the luminaire to ensure that they are free of any obstructions or

contamination (i.e. excessive dust build-up). Clean with a non-abrasive cloth if needed.

4.

Do not operate if the lens is cracked or damaged. All fasteners should be properly seated.

This explosion proof LED light fixture is field serviceable. All major internal components can be purchased 
from Larson Electronics and installed by a licensed electrician with basic tools. Contact the manufacturer for 
replacement parts.