UNIT AND LAMP INSTALLATION, REPLACEMENT, OR CLEANING

IN ORDER TO PERFORM THIS TASK, BE SURE TO WEAR THE FOLLOWING SAFETY 

EQUIPMENT: SAFETY  GLASSES OR

 

A FACE SHIELD, AS WELL AS GLOVES.

!

WARNING

         

Always disconnect power to the unit before performing any service or maintenance.

Ultraviolet lamps are easily damaged and may cause injury if broken.  Exercise care when 
handling.

!

CAUTION

1.

Disconnect power to the HVAC system.

2. M

ark the centers of the four (4) mounting holes

 

and edges of the rectangular openings for lamp assembly

.

!

CAUTION

     Mechanical hazard. Duct sheet metal has sharp edges. Wear protective gloves when 

working on or around duct sheet metal.

3.

Cut out the rectangular openings for lamp assembly. Remove burrs and sharp edges where possible.

4.

Test fit unit to duct. Lamp assembly should pass through rectangular opening, with no interference. Base plate

 

should fit flush to duct and mounting holes of the base plate should be aligned with the center marks on duct.

5.

Remove unit from duct; make any adjustments necessary until unit fits correctly.

6. Install lamp(s) in Air Duct Disinfection Systems. To install, insert lamp pin into spring-loaded lampholder. 

Carefully press lamp against the spring-loaded lampholder. Align upper lamp pin with stationary lampholder. 

Slowly ease the pressure until lamp is fully seated in lampholders.

7. Verify that the lamp is properly seated.
8. Repeat until all lamps have been properly installed.
9. Moisten a clean, lint-free cloth with denatured alcohol and wipe each lamp.

10. Clean the outer surface of duct around cutouts.
11. Fit the Air Duct Disinfection Systems into duct, align with the mounting hardware locations. (You must use a 

minimum of 4 screws)

12. Insert No.18 x 1/2”  or No. 8-8 x 1/2”, depending on the modeled ordered, mounting hardware into each of the 

marked centers, screw in approximately half their length.

13. Finish tightening hardware.
14. Plug Air Duct Disinfection Systems into properly grounded, electrical outlet. If unit is supplied without a plug for 

direct wiring, connect wire leads to appropriate power connections. All wiring must comply with applicable 

state, local and national electrical and mechanical codes.

 

Ultraviolet lamps are easily damaged and may cause injury if broken. Exercise care when handling.

!

CAUTION

!

!

!

!

Larson Electronics, LLC

 

 Phone: (800) 369-6671 

 Fax: (903) 498-3364 

 www.larsonelectronics.com 

of 

10

 

We strongly encourage a licensed electrician install this product,

 in 

all locations especially in outdoor areas where weatherproofing may be 

required.

Attach supply line wires to the appropriate light fixture wires as 

shown in the diagram 

 

Secure each pair of wires according to the diagram. Utilize a junction box 

or similar device and take precautionary steps for weatherproofing all 

connections if installed in a location where water may come in contact with 

the unit. Ensure the unit is properly grounded and that wiring is done 

according to all local and national electrical/building codes.

Summary of Contents for IND-HVAC-DTW-UVC-R1-SS Series

Page 1: ...ons when packaging equipment to prevent damage Carefully inspect and report all damages Do not install damaged equipment Follow all instructions on any labels or tags Carefully inspect all packing mat...

Page 2: ...pictorial is used to identify components which must not be disposed of in trash SAFETY INSTRUCTIONS To guard against injury basic safety precautions should be observed including the following 1 Read...

Page 3: ...harsh environments PRINCIPLE OF OPERATION The design has been carefully conceived to provide adequate germicidal ultraviolet dosage for air stream or surface disinfection in new or existing HVAC Heati...

Page 4: ...the safety or effectiveness of the installation UNPACKING IN ORDER TO PERFORM THIS TASK BE SURE TO WEAR THE FOLLOWING SAFETY EQUIPMENT SAFETY GLASSES OR A FACE SHIELD AS WELL AS GLOVES Remove the Air...

Page 5: ...ssary seal all openings joints seams etc using aluminum tape or equivalent ultraviolet resistant material Prevent exposure of any plastic rubber or other non metallic materials with inadequate resista...

Page 6: ...Outside Duct Mount Opening for outside mount shown Insert unit Attach unit using the face mounting bracket and self drilling screws View inside duct INSTALLATION Larson Electronics LLC Phone 800 369...

Page 7: ...ly seated 8 Repeat until all lamps have been properly installed 9 Moisten a clean lint free cloth with denatured alcohol and wipe each lamp 10 Clean the outer surface of duct around cutouts 11 Fit the...

Page 8: ...t our Application Specialists MAINTENANCE Always disconnect power to the unit before performing any service or maintenance WARNING The Air Duct Disinfection Unit is designed to operate with a minimal...

Page 9: ...censed personnel Table 1 Troubleshooting Problem Possible Cause Corrective Action Unit not operating No electrical power Verify that the unit is connected to a live power source Power connection to fi...

Page 10: ...ht without adequate eye protection Make it a policy to never enter areas being disinfected with UV lighting systems without powering the system down first Methods of powering down depends on the optio...

Reviews: