Characteristics
Back-up protection
Ambient temperature
- 20 ... + 60 °C In case of different temperature range please consider correction factor!
Characteristic
to IEC/EN 60898
Z
B
C
D
Rated current
range
0.5 ... 32 A
6 ... 32 A
0.5 ... 32 A
0.5 ... 32 A
Loads
> Semi-
conductor
devices
> Elektric heatings
> Lighting
> Socket outlet
circuits
> Control circuits
e.t.c.
> Operating
equipment
> Light fitting
groups
> Motors
> Transformers
e.t.c.
> Operating
equipment
> Motors with
heavy starting
characteristic
e.t.c.
Normal
temperature
20 °C 30 °C
30 °C
30 °C
30 °C
Thermal overload
trip
1.05
...
1.2 I
n
1.13
...
1.45 I
n
1.13 ... 1.45 I
n
1.13 ... 1,45 I
n
1.13 ... 1.45 I
n
Thermal overload
trip 135% UL
--
--
--
1.13 ... 1.35 I
n
--
Magnetic trip
2 ... 3 I
n
3 ... 5 I
n
5... 10 I
n
10 ... 20 I
n
Fuses must be fitted upstream to protect circuit-breakers against high short-circuit currents in
high power networks. These protect the circuit-breakers against short-circuit currents of up to 50
kA. If a short-circuit occurs, both protective devices cut out simultaneously, so that the circuit-
breaker is not destroyed and remains fully functional.
Following MCBs
Type
tripping
characteristic
C, D
B, Z
B, C, D, Z
Rated
operational
current
I
th
(A)
Preceding fuse type gG
Minimal rated operational current (A)
Maximal rated
operational
current (A)
HLX-SWG-EB
1
4
- -
- -
2
8
63
3
10
6
20
10
80
10
25
16
16
40
20
20
50
32
100
25
63
40
32
80
50
40
100
50
125