6

Tripping characteristic curves

Selectivity class

3 (IEC/EN 60898)

Response value of 

short-circuit trip

The response value of the short-circuit trip is approximately 40 % higher for DC than for AC 

at 50 / 60 Hz

Rated switching capacities

Breaking capacity

6 kA resp. 10 kA

Version

Circuit breaker, current limiting with thermal and magnetic release

01546E02

Tripping Z-characteristic curve

AC MCBs

Poles

Series with 6 kA

Series with 10 kA

Voltage

(V)

Current

(kA)

Voltage

(V)

Current

(kA)

AC to IEC/EN 60898

1 - 4

I

cn

230 / 240

6

I

cn

230 / 240

10

AC to IEC/EN 60947-2 1

I

cu

240

10

I

cu

240

15

1+N, 
2

I

cu

127

30

I

cu

127

40

240

20

240

30

415

10

415

15

3, 4

I

cu

240

20

I

cu

240

30

415

10

415

15

DC to 

IEC/EN 60947-2 
(Time constante

 15 ms)

1

I

cu

 / 

I

cs

60

20

I

cu

 / 

I

cs

60

25

2

125

25

125

30

AC / DC MCBs

AC to IEC/EN 60898

1

I

cn

230

6

2

I

cn

230 / 400

6

1, 2

I

cn

120

10

2, 3

I

cn

240

10

DC to

IEC/EN 60898

1

I

cu

 / 

I

cs

220

6

2

220 / 440

6

1

I

cn

125

10

1, 2

I

cn

220

6

2

I

cn

250

10

2

I

cn

440

6

HLX-SWG-EB Series

Larson Electronics, LLC

 

  Phone: 

 

 Fax: (903) 498-3364 

  www.larsonelectronics.com 

(877) 348-9680

Summary of Contents for HLX-SWG-EB Series

Page 1: ...HLX SWG EB Series Instruction Manual...

Page 2: ...9 Servicing 13 10 Transport and Storage 13 11 Disposal 13 2 Symbols Warning This symbol indicates advice which if ignored puts your health or the ability of the device or components to function at ri...

Page 3: ...modifications or alterations to the devices impairing their explosion protection are permitted The breakers must only be fitted and operated if they are undamaged dry and clean 4 Function of Circuit B...

Page 4: ...ng cycles Isolation function yes IEC EN 60947 2 yes IEC EN 60947 2 Pulse resistance 6 kV 6 kV Utilization category A IEC EN 60947 2 A IEC EN 60947 2 Tripping characteristic B 6 40 A Tripping character...

Page 5: ...5 Tripping characteristic curves 08903E02 11514E02 HLX SWG EB Series Larson Electronics LLC Phone Fax 903 498 3364 www larsonelectronics com 877 348 9680...

Page 6: ...ith 10 kA Voltage V Current kA Voltage V Current kA AC to IEC EN 60898 1 4 Icn 230 240 6 Icn 230 240 10 AC to IEC EN 60947 2 1 Icu 240 10 Icu 240 15 1 N 2 Icu 127 30 Icu 127 40 240 20 240 30 415 10 41...

Page 7: ...load trip 135 UL 1 13 1 35 In Magnetic trip 2 3 In 3 5 In 5 10 In 10 20 In Fuses must be fitted upstream to protect circuit breakers against high short circuit currents in high power networks These pr...

Page 8: ...ON OFF whether it is switched manually or automatically Correction factors for ambient temperatures other than 30 C 10889E00 10887E00 10888E00 Type 8562 51 520 g Type 8562 52 1040 g Type 8562 53 1400...

Page 9: ...he temperature class depends upon where the protective enclosure is installed Change the Circuit Breaker at the end of its service life to guarantee ongoing protection Upstream fuse downstream Circuit...

Page 10: ...ted into an enclosure with type of protection increased safety e 04934T00 Vertical Handle at the bottom Dimensional Drawings All Dimensions in mm Subject to Alterations 5 50 117 36 97 50 25 156 146 5...

Page 11: ...re maintained remove precisely 10 17 or 21 mm of insulation see chapter Rated connection cross section The conductor must not be damaged scored when stripping the insulation Only heat resistant cables...

Page 12: ...N 60079 14 17 If necessary the clamping connections must be retightened to the relevant torques Schematic 1 pole 1 pole N 2 pole 3 pole 3 pole N 4 pole Universalcurrent 1 pole Universalcurrent 2 pole...

Page 13: ...hen establishing the intervals between checks the operating conditions degree of utilization of the Miniatur Circuit Breaker maloperation manufacturers instructions in technical documentation mechanic...

Reviews: