![background image](http://html1.mh-extra.com/html/larson-electronics/exp-sd-sfc-120v-v1/exp-sd-sfc-120v-v1_instruction-manual_676917007.webp)
EXP-SD-SFC-120V-V1
Larson Electronics, LLC
Phone: (800) 369-6671
Fax: (903) 498-3364
www.larsonelectronics.com
7
of
9
MAINTENANCE
WARNING
To avoid
a
potential electrostatic discharge (ESD), do not wipe or rub the surface of
the EXP-SD-SFC-120V-V1
sensor
module.
NOTE :
The EXP-SD-SFC-120V-V1 Smoke Detector contains no user serviceable
components and should never be opened. The 3EXP-SD-SFC-120V-V1 wiring
compartment
is
the only part of the
smoke
detector that should be opened by the
user in the field.
ROUTINE INSPECTION
Regularly scheduled maintenance is not required, however the EXP-SD-SFC-120V-V1
cover and smoke chamber should be inspected periodically when detectors are located in
abnormally dirty or dusty environments, to ensure the smoke chamber is not blocked by dirt or
debris.
The smoke detector can be tested using the same methods employed for any photo-electric
detector. Det-Tronics recommends using a test aerosol smoke dispenser for periodic
maintenance of the detector.
Figure 10-Ground Lug Locations
ALIGNMENT GUIDE
Figure 11-Alignment Guide Location
RELAY
OUTPUTS
I
NO AUX
"'
COM AUX
NC AUX
NO ALARM
COM
ALARM
NC ALARM
i)
COM FAULT
NO FAULT
PS
POWER
SUPPLY &
0-20 mA OUTPUT
P11
, ,
GROUND LUG/
0
0
PLC
2WIRE
CLASS B
RECEIVING ZONE
CHASSIS
GROUND
Figure 12-Single Detector Wiring (0-20 mA used, Relays not used)