MANUAL SELF-TEST 

The  Manual  Self-Test  function  will  immediately check the smoke chamber optics for 

9egradation. Once i(litiated,  there will be  a one second  delay before the result of  the 

check  is  active.  If  tneJe  is a  failure,  the  LED  will  shut  off  immediately  after  the  one 

second test and a critical fault will occur. If the test passes,  an alarm will  be annunciated 

while the LED remains active. 

For 

a  latching 

detector,  the 

alarm 

will 

continue until power is cycled to the unit.  If the 

test passes, but there is degradation present and approaching critical levels,  an 

advisory 

fault 

will 

occur. 

For a non-latching 

detector the 

alarm 

will 

clear 

after 10 seconds. 

Magnetic Switch 

The magnetic switch i

 used to initiate lhe Manual 

Self-Test (see  Figure 3). Apply the 

magnet  to  the  exterior  housing  and  the  LED  will  light  to  indicate  that  the  magnet  is 

detected. The LED will remain lit for at least one  second during the  test.  After 

the initial 

delay, the test status will be indicated as 

described in the "Manual Self-Test" section. 

INSTALLATION 

WARNING 

All  entries  must  contain  appropriately  rated  plugs  or  fittings.  It  is  required  that  each  plug  or  fitting  be  wrench-

tightened  to  an  appropriate  installation  torque  and  meet  the  minimum  thread  engagement  requirements  per  the 

applicable  local  standards,  codes,  and  practices  in  order  to  retain  the  defined  ratings.  PTFE  sealant  or  equivalent 

should be used on NPT threads. 

NOTE

 :

Detector  housings  must  be  electrically connected  to  earth  ground.  Internal

·

 

and  external  earth ground 

terminals are provided. For AEx (United States  Zone) installations  the  internal  ground  terminal shall be used for 

the equipment grounding connection. The external  terminal can  be used  for  supplementary  bonding  where local 

codes permit or require. 

NOTE :

The 

EXP-SD-SFC-120V-V1

  detector  uses  an  internal Intrinsically Safe  (I.S.)  Barrier. Proper  NEC 

I.S. grounding must be ensured.

GREASE/LUBRICATION

To  ease  installation  and  future  removal,  all threaded  covers,  stopping  plugs,  and  thread 

adapters must be  installed using 

thread lubricant. 

The  recommended  lubricant  is  a  silicone-free grease, available from Det-Tronics. 

For  devices  with  NPT  threads,  Teflon  tape  or thread seal lubricant must be used for enhanced 

sealing 

c

apa

_

bilitie

s. 

IDENTIFICATION OF DETECTOR MOUNTING LOCATIONS 

The  most  effective  number  and  placement  of 

detectors varies depending on the conditions on site. The individual designing the 

installation  must  often  rely  o

n

experience  and  sound  judgment 

to  determine  the  detector  quantity  and  best 

locations  to 

adequately protect the area. Note that it is typically  advantageous  to  locate  detectors where they are accessible for maintenance. 

For  additional  information  on  detector  location 

and  spacing,  visit  the  National  Fire  Protection 

Association's  website 

(www.nfpa.org)  for  the 

NFPA Number 72, the Standard on Automatic Fire 

Detectors. 

PROTECTION AGAINST MOISTURE DAMAGE 

It  is  important  to  take  proper  precautions  during 

installation  to  ensure  that  moisture  will  not  come 

in  contact  with  the  electrical 

connections  of the system.  The  integrity  of  the  system  regarding moisture  protection  must  be  maintained  for proper  operation 

and is the responsibility of the installer. 

If  conduit  is  used,  the  use  of  proper  conduit  installation  techniques,  breathers,  glands,  and seals  is  required  to  prevent  waler 

ingress and/or maintain the explosion-proof rating. 

Conduit  drains  must  be  installed  at  water  collection  points  to  automatically  drain  accumulated  moisture.  Conduit 

breathers should  be  installed  at  upper  locations  to provide  ventilation  and  allow  water  vapor  to escape.  At least  one breather 

should be used with each drain. 

Conduit  raceways  should  be  inclined  so  that water  will  flow  to  low  points  for  drainage  and will  not  collect inside  enclosures  or  on 

conduit 

seals.  If this is not possible, install conduit drains above the seals to prevent the collection of water or install a drain loop below 

the detector with a conduit drain at the lowest point of the loop. 

Summary of Contents for EXP-SD-SFC-120V-V1

Page 1: ...ILIAR WITH ANY ASPECT OF THIS INSTRUCTION SHEET CONSULT AN ELECTRICIAN THERE ARE NO SERVICEABLE PARTS INSIDE WARNING MAKE SURE POWER IS TURNED OFF BEFORE STARTING THE INSTALLATION OR PERFORMING ANY MAINTENANCE RISK OF FIRE ELECTRIC SHOCK DISCONNECT POWER AT BREAKER BEFORE INSTALLING OR SERVICING RISK OF PERSONAL INJURY FIXTURE MAY BECOME UNSTABLE OR DAMAGED IF NOT INSTALLED PROPERLY RISK OF BURN A...

Page 2: ...ector is initially powered up a warm up period of 1 2 seconds is allotted for internal checks and communication During this time the LED is off and the current level is 3 rQA After the checks are completed normal operation will be indicated by the LED flashing every four seconds current level is 4 mA If the detector is unable to reach the normal operating mode the warm up period may extend to five...

Page 3: ... indicates normal operation and notifies personnel of an alarm Table 2 indicates t le condition of the LED for each status Table 2 Detector Status Indicator Detector Status LED Indicator Power On Normal Operation Steady Off 1 blink on every 4 seconds Alarm Steady On LATCHING A detector configured for latching operation will remain in an alarm state indefinitely after an alarm occurs NON LATCHING A...

Page 4: ... S Barrier Proper NEC I S grounding must be ensured GREASE LUBRICATION To ease installation and future removal all threaded covers stopping plugs and thread adapters must be installed using thread lubricant The recommended lubricant is a silicone free grease available from Det Tronics For devices with NPT threads Teflon tape or thread seal lubricant must be used for enhanced sealing capa_bilities ...

Page 5: ...act location of the detector must be determined by an evaluation based on supplemented engineering judgement or if possible by field tests IMPORTANT Whenever possible select a mounting orientation where the LED is visible to personnel within the area m 1 LEO__J NOTE MAKE CERTAIN THAT THE LED IS POSmONEO WHERE VISIBLE SIDE WALL MOUNT THE DETECTOR Using three No 8 flat head screws or equivalent plac...

Page 6: ...instructions when wiring the EXP SD SFC 120V V1 detector 1 Slightly loosen the three setscrews located on the retaining ring RETAINING RING 2 Unscrew the retaining ring to gain access to the wiring terminals see Figure 8 and complete the installation of the system conduit Feed the external wiring through the remaining junction box entry or M25 to 3 4 inch adapter When installing the junction box u...

Page 7: ...quired however the EXP SD SFC 120V V1 cover and smoke chamber should be inspected periodically when detectors are located in abnormally dirty or dusty environments to ensure the smoke chamber is not blocked by dirt or debris The smoke detector can be tested using the same methods employed for any photo electric detector Det Tronics recommends using a test aerosol smoke dispenser for periodic maint...

Page 8: ...mA not used Relays used RELAY OUTPUTS NOAU COMAUX NC AUX NOALARM COM ALARM NC ALARM COM FAULT NO FAULT PS POWER SUPPLY RELAY OUTPUTS NOAUX COM AUX NC AUX NOALARM COM ALARM NC ALARM COM FAULT NO FAULT PS I ll POWER SUPPLY RELAY OUTPUTS NC AUX NOALARM SUPPLY I I I I I I I I I I x COM ALARM NCALARM Vin I 2 I C 0 COM FAULT NO FAULT PS Figure 14 Multiple Detector Wiring 0 20 mA used Relays not used 0 0...

Page 9: ...e function and or safety of this device and could affect the life of the equipment Always check for damaged or worn out parts before using the device Store it in a secure place out of the reach of children when not in use Inspect for good working condition prior to storage and before re use REPLACEMENT PARTS The EXP SD SFC 120V V1 is designed to provide years of reliable performance Should the nee...

Reviews: