background image

EXP-SD-SFC-120V-V1

Larson Electronics, LLC

 

  Phone: (800) 369-6671 

 Fax: (903) 498-3364 

  www.larsonelectronics.com 

5

 of 

9

 

POWER SUPPLY REQUIREMENTS 

Calculate  the  total  detection  system  power  consumption  rate  in  watts  from  cold 

start-up.  Select  a  power  supply  with  adequate capability 

for  the calculated  load.  Ensure 

that the selected power supply provides sufficient regulated and 

filtered output power for 

the entire  system.  If  a  back-up  power  system  is  required,  a  float-type  battery  charging 

system is recommended.  If an existing  source  of power  is being used,  verify that system 

requirements are met. 

TRANSPORT COVER 

The Transport  Cover  (see  Figure  4)  keeps  dust 

and particles out of the smoke chamber 

that may enter during transport,  handling, or installation. It should remain fastened on the 

detector through the installation process. 

IMPORTANT 

Remove  the  cover 

only 

after  installation is  complete  and  prior  to  powering 

the detector for the first time.

TRANSPORT 

COVER 

MOUNTING LOCATION OPTIONS 

Ceiling Mount 

The EXP-SD-SFC-120V-V1 is intended for surface mounting.  It is normally mounted on the 

ceiling no less than six  inches from  a side wall (See  Figure 5).  The exact  location of the 

detector  must  be  determined  by  an  evaluation  based  on  engineering  judgement,  or  if 

possible, by field tests. 

NOTE:  MAKE  CERTAIN  THAT  THE LEO 

IS POSITIONED WHERE VISIBLE. 

Wall Mount 

The 

EXP-SD-SFC-120V-V1

 can also be mounted on a side wall (see Figure 6). The exact 

location of the detector must  be  determined  by  an  evaluation  based on  supplemented 

engineering  judgement,  or  if 

possible, by field tests. 

IMPORTANT 

Whenever  possible,  select 

mounting  orientation  where  the 

LED 

is 

visible  to personnel within the area. 

� 

m/� 

,---

LEO__J 

NOTE: 

MAKE CERTAIN THAT THE LED 

'-

IS POSmONEO WHERE VISIBLE. 

SIDE 

WALL 

� 

MOUNT THE DETECTOR 

Using  three  No.  8  flat  head  screws  (or  equivalent) 

placed  through  the  counter 

bored  holes  in  the detector flange,  secure the  detector  junction  box to the surface 

location. 

WIRING CABLE REQUIREMENTS 

Always  use  proper  temperature  rated  cabling 

type  and  diameter  for  input 

power  as  well  as 

output  signal  wiring.  14  to  18  AWG  shielded 

stranded 

copper wire is recommended. 

The field wiring terminal connections are certified 

for  a single  wire in size from 0.2 

to 2.5  mm2  (or 

two  conductors  with same  cross  section  0.2  to 

0. 75 mm2).  The 

screws must be tightened down with a torque 0.4 to 0.5  N•m. The  metal housing 

must be electrically connected to earth ground.

A  minimum  of  12  Vdc  must  be  present  at  the 

EXP-SD-SFC-120V-V1

  to  ensure 

proper  operation.  The  maximum 

cable  length  from  power  source  to 

EXP-SD-

SFC-120V-V1

  is 

2000 feet.  When the 

EXP-SD-SFC-120V-V1

 Smoke  Detector  is 

mounted remotely using an STB termination box, maximum cable length from 

EXP-

SD-SFC-120V-V1

 to STB is 500 feet. 

WARNING

 

For  field connections, use wires/cables that are rated at 

20°C 

greater than the maximum ambient temperature. 

NOTE :

In  applications  where  the  wiringg  is  installed  in  conduit,  dedicated  conduit  is  recommended.  Avoid  low 

frequency, high voltage, and  non-signaling  conductors  to prevent nuisance EM/ problems. 

Summary of Contents for EXP-SD-SFC-120V-V1

Page 1: ...ILIAR WITH ANY ASPECT OF THIS INSTRUCTION SHEET CONSULT AN ELECTRICIAN THERE ARE NO SERVICEABLE PARTS INSIDE WARNING MAKE SURE POWER IS TURNED OFF BEFORE STARTING THE INSTALLATION OR PERFORMING ANY MAINTENANCE RISK OF FIRE ELECTRIC SHOCK DISCONNECT POWER AT BREAKER BEFORE INSTALLING OR SERVICING RISK OF PERSONAL INJURY FIXTURE MAY BECOME UNSTABLE OR DAMAGED IF NOT INSTALLED PROPERLY RISK OF BURN A...

Page 2: ...ector is initially powered up a warm up period of 1 2 seconds is allotted for internal checks and communication During this time the LED is off and the current level is 3 rQA After the checks are completed normal operation will be indicated by the LED flashing every four seconds current level is 4 mA If the detector is unable to reach the normal operating mode the warm up period may extend to five...

Page 3: ... indicates normal operation and notifies personnel of an alarm Table 2 indicates t le condition of the LED for each status Table 2 Detector Status Indicator Detector Status LED Indicator Power On Normal Operation Steady Off 1 blink on every 4 seconds Alarm Steady On LATCHING A detector configured for latching operation will remain in an alarm state indefinitely after an alarm occurs NON LATCHING A...

Page 4: ... S Barrier Proper NEC I S grounding must be ensured GREASE LUBRICATION To ease installation and future removal all threaded covers stopping plugs and thread adapters must be installed using thread lubricant The recommended lubricant is a silicone free grease available from Det Tronics For devices with NPT threads Teflon tape or thread seal lubricant must be used for enhanced sealing capa_bilities ...

Page 5: ...act location of the detector must be determined by an evaluation based on supplemented engineering judgement or if possible by field tests IMPORTANT Whenever possible select a mounting orientation where the LED is visible to personnel within the area m 1 LEO__J NOTE MAKE CERTAIN THAT THE LED IS POSmONEO WHERE VISIBLE SIDE WALL MOUNT THE DETECTOR Using three No 8 flat head screws or equivalent plac...

Page 6: ...instructions when wiring the EXP SD SFC 120V V1 detector 1 Slightly loosen the three setscrews located on the retaining ring RETAINING RING 2 Unscrew the retaining ring to gain access to the wiring terminals see Figure 8 and complete the installation of the system conduit Feed the external wiring through the remaining junction box entry or M25 to 3 4 inch adapter When installing the junction box u...

Page 7: ...quired however the EXP SD SFC 120V V1 cover and smoke chamber should be inspected periodically when detectors are located in abnormally dirty or dusty environments to ensure the smoke chamber is not blocked by dirt or debris The smoke detector can be tested using the same methods employed for any photo electric detector Det Tronics recommends using a test aerosol smoke dispenser for periodic maint...

Page 8: ...mA not used Relays used RELAY OUTPUTS NOAU COMAUX NC AUX NOALARM COM ALARM NC ALARM COM FAULT NO FAULT PS POWER SUPPLY RELAY OUTPUTS NOAUX COM AUX NC AUX NOALARM COM ALARM NC ALARM COM FAULT NO FAULT PS I ll POWER SUPPLY RELAY OUTPUTS NC AUX NOALARM SUPPLY I I I I I I I I I I x COM ALARM NCALARM Vin I 2 I C 0 COM FAULT NO FAULT PS Figure 14 Multiple Detector Wiring 0 20 mA used Relays not used 0 0...

Page 9: ...e function and or safety of this device and could affect the life of the equipment Always check for damaged or worn out parts before using the device Store it in a secure place out of the reach of children when not in use Inspect for good working condition prior to storage and before re use REPLACEMENT PARTS The EXP SD SFC 120V V1 is designed to provide years of reliable performance Should the nee...

Reviews: