background image

EPS-2XPB-SG-AT-V3

Larson Electronics, LLC

 

  Phone: (800) 369-6671 

 Fax: (903) 498-3364 

  www.larsonelectronics.com 

of 

3

 

INSTALLATION 

1.

Mount the back box by means of mounting lugs. Install conduit nipple and sealing fittings, to be installed on each

 

conduit 

entrance or exit to the enclosure back box in Class I and Class II areas. Thread conduit into sealing fitting

 

(Note: For Class I 

areas, the conduit should engage [5] full threads.)

2.

The conduit threads should be lubricated with a non-electrical insulating lubricant or pipe joint compound that will

 

not promote 

corrosion or chemically attack aluminum.

3.

After conduit system has been properly installed, pull the wires and make electrical connections as required. The

 

electrical 

circuits and ground continuity should be checked with an instrument approved for the area. Notice:

 

Connect only copper wire to 

this device.

4.

All conduits entering or leaving the enclosure must be sealed within 18” of the enclosure with listed sealing

 

fittings. Caution 

must be taken during installation to be sure that the ground flange flame joints of the cover and

 

box are not scratched, nicked, 

or damaged. Before assembly of the cover to the box, the mating ground surfaces

 

of both the box and cover should be wiped 

clean to assure that the ground flame joint will be free of all foreign

 

particles such as lint, dust or dirt.

5.

After tightly bolting the cover assembly/assemblies to the enclosure, all box to cover flame joints should be

 

checked with a 

0.0015” thick feeler gauge such that the gauge will not enter the flame path more than 1/8” at any

 

point.

MAINTENANCE 

All moving shafts should be lubricated 
occasionally to prevent binding. Only use a 
lubricant which is suitable for use with 
aluminum or stainless steel. If devices are 
to be installed in corrosive areas which will 
attack aluminum alloys containing less than 
0.4% copper (boxes and covers) and 303 
stainless steel (mostly shafts), the device 
should be suitably protected from the 
corrosive material.  

CAUTION: 

To prevent ignition of 

hazardous atmospheres, disconnect from 
the supply circuits before opening the 
enclosure; keep tightly closed while circuits 
are energized. 

OPERATION

The EPS-2XPB-SG-AT-V3 offers adjusted timing control of motors in hazardous locations. This explosion proof switch is designed to 

operate with 100-240V AC/DC 50/60 Hz and comes with a 10-amp rating (at 600V AC). The unit requires sealing fittings and compound 

within 18 inches of conduit entrances. A solid-state, encapsulated time delay relay can be found inside the switch, which offers an 

adjustable timer range of 10 seconds to 170 minutes. When the button is engaged, the circuit stays closed, keeping the connected motor 

or device running for the set duration (between 10 seconds - 170 minutes in 1 second increments). The timer component features a 

repeating accuracy value of +/- 0.5% and a setting accuracy value of +/- 2%. Controls for the explosion proof timer includes: (1) green 

push button - start timer and (1) red push button - stop timer early before set time.

Reviews: