LA-ON-RACK 6K/10K
09: Battery backup time setting
Interface Setting
Parameter 3:
000~999:
Set the maximum backup time from 0min to 999min. UPS
will shut down to protect battery after backup time arrives. The
default value is 990min.
DIS:
Disable battery discharge protection and backup time will
depend on battery capacity.
10: Programmable output setting
Note
:
This function is not supported by the Rack model.
Interface Setting
Parameter 3:
Set programmable output. You may choose the
following three options:
ON:
Programmable output is manually switched on timelessly.
OFF:
Programmable output is manually switched off. However, if
UPS restarts, this setting will automatically go to “ATO” status.
ATO:
Programmable output is automatically turned on or cut off
according to battery or load status. When the battery voltage is lower
than the setting point, or shutdown time arrives, the programmable
output will be cut off automatically. After the utility is recovering, the
output will turn on automatically. If overload happens, the
programmable output also will be cut off automatically. If it happens 3
times, the programmable output will be cut off until it is manually
switched on.
11: Shutdown point for programmable output
Note
:
This function is not supported by the Rack model.
Interface Setting
Parameter 2: 001.
Set shutdown time for programmable output.
Parameter 3: Shutdown time in minutes.
Setting range is from 0 to 300. When shutdown time arrives, the
programmable output terminal will be cut off. The default value is 30
minutes.
Parameter 2: 002
Set shutdown voltage for programmable output.
Parameter 3: Shutdown voltage in V.
Setting range is from 11.2 to 13.6. If the battery voltage is less than
the setting point, the programmable output will be cut off. The default
value is 11.2V.
12: Hot standby function enable/disable
Interface Setting
Parameter 2: HS.H
Enable or disable Hot standby function. You may choose following
two options in
Parameter 3
:
YES:
Hot standby function is enabled. It means that the current UPS
is set to host of the hot standby function, and it will restart after AC
recovery even without battery connected.
NO:
Hot standby function is disabled. The UPS is running at normal
mode and can’t restart without battery