LA-ON-RACK 6K/10K 

2.3. Single UPS Installation 

Installation and wiring must be performed in accordance with the local electric laws/regulations and execute the 
following instructions by professional personnel. 
1) 

Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid 

the hazards of electric shock or fire. 

NOTE:

 Do not use the wall receptacle as the input power source for the UPS, as its rated current is less 

than the UPS’s maximum input current. Otherwise the receptacle may be burned and destroyed. 

2)  Switch off the mains switch in the building before installation. 
3)  Turn off all the connected devices before connecting to the UPS. 
4)  Prepare wires based on the following table: 

Wiring spec (AWG) 

Model 

Input Output Battery Ground 

6KR 10  10 

 

10 

6KR-L 10 

10 

10 

10 

10KR 

8  8 

10KR-L 8 

NOTE 1: 

The cable for 6K/6K-L should be able to withstand over 40A current. It is recommended to use 

10AWG or thicker wire for safety and efficiency. 

NOTE 2: 

The cable for 10K/10KL should be able to withstand over 63A current. It is recommended to use 

8AWG or thicker wire for safety and efficiency. 

NOTE 3: 

The selections for color of wires should be followed by the local electrical laws and regulations. 

5)  Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the 

following terminal block diagrams: (Connect the earth wire first when making wire connection. Disconnect 
the earth wire last when making wire disconnection!) 

 

 

Terminal Block wiring diagram for 6KR(L)/10KR(L) 

NOTE 1: 

Make sure that the wires are connected tightly with the terminals. 

 

NOTE 2: 

There are two kinds of outputs: output terminal/outlets and programmable terminal. Please 

connect non-critical devices to the programmable terminal and critical devices to the output 
terminal/outlets. During power failure, you may extend the backup time to critical devices by setting shorter 
backup time for non-critical devices. 

NOTE 3: 

Please install the output breaker between the output terminal and the load, and the breaker 

should be qualified with leakage current protective function if necessary. 

6) 

Insert the EPO plug into the EPO slot on the rear panel. 

7) 

Put the terminal block cover back to the rear panel of the UPS. 

Input Neutral 

Input Line 

Ground 

Output Line 

Output Neutral 

Summary of Contents for 6KR

Page 1: ...Online UPS 6K 10K RACK Uninterruptible Power Supply System USER MANUAL EN...

Page 2: ...d operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all...

Page 3: ...TION 7 2 4 UPS INSTALLATION FOR PARALLEL SYSTEM 8 2 5 SOFTWARE INSTALLATION 9 3 OPERATIONS 10 3 1 BUTTON OPERATION 10 3 2 LED INDICATORS AND LCD PANEL 10 3 3 AUDIBLE ALARM 12 3 4 SINGLE UPS OPERATION...

Page 4: ...Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over the...

Page 5: ...nnect the mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 5 Standards Safety IEC EN 62040 1...

Page 6: ...toring software CD One RS 232 cable option One USB cable One EPO plug One parallel cable only available for parallel model One share current cable only available for parallel model One battery cable o...

Page 7: ...Cooling fan 8 External maintenance bypass switch port 9 Maintenance bypass switch 10 Input circuit breaker 11 Output receptacles connect to mission critical loads 12 Output circuit breaker for recepta...

Page 8: ...A current It is recommended to use 8AWG or thicker wire for safety and efficiency NOTE 3 The selections for color of wires should be followed by the local electrical laws and regulations 5 Remove the...

Page 9: ...etting simultaneously The connection with wrong battery voltage may cause permanent damage of the UPS Make sure the voltage of the battery pack is correct Pay highly attention to the polarity marking...

Page 10: ...timal computer system protection install UPS monitoring software to fully configure UPS shutdown Install CD or visit the website http www power software download com for the latest software version Di...

Page 11: ...s this button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key P...

Page 12: ...level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the output is short Programmable output information Indicates that the programmable outputs are working Mode operation inf...

Page 13: ...tery pack at ON position the step only available for long run model Then set the input breaker at ON position At this time the fan is running and the UPS supplies power to the loads via the bypass The...

Page 14: ...ation 1 When the UPS is in Battery mode the buzzer will beep according to different battery capacity If the battery capacity is more than 25 the buzzer will beep once every 4 seconds If the battery vo...

Page 15: ...g alarms can t be muted unless the error is fixed Please refer to section 3 3 for the details 11 Operation in Fault mode 1 When Fault LED illuminates and the buzzer beeps continuously it means that th...

Page 16: ...ter all of them transfer to Bypass mode turn on the output breaker of each unit 7 Turn on the UPSs in the AC mode and then the parallel system connection is complete 2 Add one new unit into the parall...

Page 17: ...ves There are 15 programs to set up Refer to below table Parameter 2 and parameter 3 are the setting options or values for each program 15 programs available list for parameter 1 Code Description Bypa...

Page 18: ...utility frequency If it is from 46Hz to 54Hz the output frequency will be 50 0Hz If it is from 56Hz to 64Hz the output frequency will be 60 0Hz ATO is default setting Parameter 3 Frequency mode Settin...

Page 19: ...0 of the nominal voltage Parameter 3 High voltage point in ECO mode The setting range is from 5 to 10 of the nominal voltage 07 Frequency range for ECO mode Interface Setting Parameter 2 Set low volta...

Page 20: ...ens the programmable output also will be cut off automatically If it happens 3 times the programmable output will be cut off until it is manually switched on 11 Shutdown point for programmable output...

Page 21: ...ger voltage We strongly suggest to use the default value 0 Any modification should be suitable to battery specifications 15 Output voltage adjustment Interface Setting Parameter 2 you may choose Add o...

Page 22: ...Battery mode LCD display Description When input voltage is within acceptable range and bypass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two minutes Bypass mode LCD di...

Page 23: ...1 None Output circuit circuited 36 None High Inverter voltage 12 None Over temperature 41 None Low Inverter voltage 13 None CPU communication failure 42 None Inverter output short circuited 14 Overloa...

Page 24: ...cked in the Bypass mode Connected devices are fed directly by the mains Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD...

Page 25: ...d with the required precautionary measures may replace batteries and supervise operations Unauthorized persons must be kept well away from the batteries Verify that no voltage between the battery term...

Page 26: ...er to 90 capacity 4 hours recover to 90 capacity Charging Current 2 A 10 max Standard Model Charging Voltage 14 4 V 1 Type Depending on applications Numbers 18 20 Charging Current 2 A 10 max Long run...

Reviews: