4. Trouble Shooting 

If the UPS system does not operate correctly, please solve the problem by using the table below.   

Symptom Possible 

cause 

Remedy 

No indication and alarm in the front 
display panel even though the mains is 
normal.  

The AC input power is not 
connected well. 

Check if input cable firmly 
connected to the mains.   

The icon 

and the warning code 

 flash on LCD display and alarm 

beeps every second. 

EPO function is enabled. 

Set the circuit in closed position 
to disable EPO function.   

The icon 

and 

 flash on LCD 

display and alarm beeps every second. 

The external or internal battery 
is incorrectly connected. 

Check if all batteries are 
connected well. 

Fault code is shown as 28, the icon 

 lights on LCD display, and 

alarm beeps continuously. 

Battery voltage is too low or the 
charger is fault. 

Contact your dealer. 

UPS is overload.   

Remove excess loads from UPS 
output. 

UPS is overloaded. Devices 
connected to the UPS are fed 
directly by the electrical network 
via the Bypass. 

Remove excess loads from UPS 
output. 

The icon 

 and

 flash  on 

LCD display and alarm beeps twice 
every second. 

After repetitive overloads, the 
UPS is locked in the Bypass 
mode. Connected devices are 
fed directly by the mains. 

Remove excess loads from UPS 
output first. Then shut down the 
UPS and restart it. 

Fault code is shown as 43. The icon 

 lights on LCD display and 

alarm beeps continuously. 

UPS is overload too long and 
becomes fault. Then UPS shut 
down automatically. 

Remove excess loads from UPS 
output and restart it. 

Fault code is shown as 14, the icon 

 lights on LCD display, and 

alarm beeps continuously. 

The UPS shut down 
automatically because short 
circuit occurs on the UPS 
output. 

Check output wiring and if 
connected devices are in short 
circuit status. 

Fault code is shown as 1, 2, 3, 4, 5, 11, 
12, 13, 14,1A, 21, 24,28, 35, 36, 
41 ,42or 43 on LCD display and alarm 
beeps continuously. 

A UPS internal fault has 
occurred. There are two 
possible results: 
1. The load is still supplied, but 
directly from AC power via 
bypass.  
2. The load is no longer 
supplied by power.   

Contact your dealer 

Batteries are not fully charged 

Charge the batteries for at least 
7 hours and then check 
capacity. If the problem still 
persists, consult your dealer.   

Battery backup time is shorter than 
nominal value 

Batteries defect 

Contact your dealer to replace 
the battery. 

The icon 

and 

 flash on LCD 

display and alarm beeps every second. 

Fan is locked or not working; or 
the UPS temperature is too 
high. 

Check fans and notify dealer.   

Summary of Contents for 6KR

Page 1: ...Online UPS 6K 10K RACK Uninterruptible Power Supply System USER MANUAL EN...

Page 2: ...d operating instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all...

Page 3: ...TION 7 2 4 UPS INSTALLATION FOR PARALLEL SYSTEM 8 2 5 SOFTWARE INSTALLATION 9 3 OPERATIONS 10 3 1 BUTTON OPERATION 10 3 2 LED INDICATORS AND LCD PANEL 10 3 3 AUDIBLE ALARM 12 3 4 SINGLE UPS OPERATION...

Page 4: ...Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal Place cables in such a way that no one can step on or trip over the...

Page 5: ...nnect the mains Ensure that no liquid or other foreign objects can enter into the UPS system The UPS can be operated by any individuals with no previous experience 1 5 Standards Safety IEC EN 62040 1...

Page 6: ...toring software CD One RS 232 cable option One USB cable One EPO plug One parallel cable only available for parallel model One share current cable only available for parallel model One battery cable o...

Page 7: ...Cooling fan 8 External maintenance bypass switch port 9 Maintenance bypass switch 10 Input circuit breaker 11 Output receptacles connect to mission critical loads 12 Output circuit breaker for recepta...

Page 8: ...A current It is recommended to use 8AWG or thicker wire for safety and efficiency NOTE 3 The selections for color of wires should be followed by the local electrical laws and regulations 5 Remove the...

Page 9: ...etting simultaneously The connection with wrong battery voltage may cause permanent damage of the UPS Make sure the voltage of the battery pack is correct Pay highly attention to the polarity marking...

Page 10: ...timal computer system protection install UPS monitoring software to fully configure UPS shutdown Install CD or visit the website http www power software download com for the latest software version Di...

Page 11: ...s this button to display next selection in setting menu Mute Down Button Mute the alarm Press and hold the button more than 0 5s to mute the buzzer Please refer to section 3 4 9 for details Down key P...

Page 12: ...level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the output is short Programmable output information Indicates that the programmable outputs are working Mode operation inf...

Page 13: ...tery pack at ON position the step only available for long run model Then set the input breaker at ON position At this time the fan is running and the UPS supplies power to the loads via the bypass The...

Page 14: ...ation 1 When the UPS is in Battery mode the buzzer will beep according to different battery capacity If the battery capacity is more than 25 the buzzer will beep once every 4 seconds If the battery vo...

Page 15: ...g alarms can t be muted unless the error is fixed Please refer to section 3 3 for the details 11 Operation in Fault mode 1 When Fault LED illuminates and the buzzer beeps continuously it means that th...

Page 16: ...ter all of them transfer to Bypass mode turn on the output breaker of each unit 7 Turn on the UPSs in the AC mode and then the parallel system connection is complete 2 Add one new unit into the parall...

Page 17: ...ves There are 15 programs to set up Refer to below table Parameter 2 and parameter 3 are the setting options or values for each program 15 programs available list for parameter 1 Code Description Bypa...

Page 18: ...utility frequency If it is from 46Hz to 54Hz the output frequency will be 50 0Hz If it is from 56Hz to 64Hz the output frequency will be 60 0Hz ATO is default setting Parameter 3 Frequency mode Settin...

Page 19: ...0 of the nominal voltage Parameter 3 High voltage point in ECO mode The setting range is from 5 to 10 of the nominal voltage 07 Frequency range for ECO mode Interface Setting Parameter 2 Set low volta...

Page 20: ...ens the programmable output also will be cut off automatically If it happens 3 times the programmable output will be cut off until it is manually switched on 11 Shutdown point for programmable output...

Page 21: ...ger voltage We strongly suggest to use the default value 0 Any modification should be suitable to battery specifications 15 Output voltage adjustment Interface Setting Parameter 2 you may choose Add o...

Page 22: ...Battery mode LCD display Description When input voltage is within acceptable range and bypass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two minutes Bypass mode LCD di...

Page 23: ...1 None Output circuit circuited 36 None High Inverter voltage 12 None Over temperature 41 None Low Inverter voltage 13 None CPU communication failure 42 None Inverter output short circuited 14 Overloa...