Meter Front Panel Features Released
9/31
Cashpower Three Phase V11
– User Guide
© Gyr (Pty) Ltd
3.3
Rate of Consumption Indicator (Rate LED)
This red
LED provides the
reference
output for verifying the meter’s metrological accuracy. It also
provides a visual indication of instantaneous power consumption.
The
meter constant
for the 3-Phase meter is set to 1000 impulses/kWh. The
rate
LED will therefore
flash 1000 times for every kWh of energy consumed.
3.4
Optical Communications Port
This port enables data to be transferred to and from the meter (e.g. the accessing of various registers
or downloading of new parameters) us
ing a portable interrogation device. The optical port’s
communication protocol complies with IEC 62056-21 Mode C.
3.5
Status Indicator
This yellow LED gives a quick, visual indication of several important meter statuses and provides a
useful diagnostic function to assist utility staff. During normal operation it flashes once every 5
seconds (effectively a
power on
indication). Two or more flashes occurring at regular intervals
indicate other status conditions as follows:
2 flashes
Meter
error
This is a fault condition and requires a
service call-out. The load switch will
be open
6 flashes
Meter
not initialised
The meter will not accept credit until
the appropriate vending keys are
entered
3 flashes
Meter
tampered
The load switch will be open
7 flashes
Meter
decommissioned
The load switch will be open
4 flashes
Meter
out of credit
The load switch will be open
8 flashes
Customer interface unit
keypad
locked out
The customer is temporarily inhibited
from entering vouchers due to
incorrect number entry on previous
attempts
5 flashes
Power limit
exceeded
The load switch will be open
9 flashes
Waiting for
manual load switch
closure
This indicates that the customer is
required to press any key on the
keypad of either the meter or the
customer interface unit to safely effect
load switch closure
3.6
Customer Interface Unit Communications Indicator
This green LED gives a visual indication of communication status with a remotely connected customer
interface unit:
During normal operation, with a customer interface unit connected to the energy management unit,
this LED flickers continuously at the transmitted data rate.
If there is no communication with a customer interface unit, the LED glows steadily. This would be
the case if the customer interface unit were faulty or the communications lines broken (open
circuit).
If the communication line is short-circuited, the LED is off.