Pipe Sizing Chart for Natural Gas

The following chart is based on gas pressure in the 
range 0-0.5 psi, specific gravity of 0.6 and pressure 
loss of 0.5" W.C. Numbers are for straight schedule 40 
pipe; fittings further reduce capacity. For example, in 1" 
size, an elbow is equivalent to about 2.6 feet of pipe 
and a tee is equivalent to about 5.2 feet of pipe.

Maximum capacity of pipe in cubic feet/hr of natural gas 
(Multiply values by 1000 to get nominal BTU/hr 
capacity.

LP-Gas (Liquid petroleum gas or propane)

LP-gas is gas compressed into liquid form for easy 
transportation and storage. It is also known as propane 
or bottle gas. (Propane tanks are not supplied with this 
equipment.)
LP-gas is flammable, is always contained under 
pressure and the liquid can freeze skin. Therefore, in 
the interest of safety, it is important to understand the 
basic facts about LP-gas and LP-gas containers.

Federal DOT (Department of Transportation) regula-
tions require periodic inspections and re-qualifications 
of cylinders. DO NOT USE damaged or rusted 
containers.
DO NOT store LP-gas containers indoors or in 
enclosed areas. Do not expose LP-gas container to 
heat. Always store with service valve closed and 
plugged as required.

CAUTION: Use LP-gas containers in proper position. 

Propane tanks, gas bottles will not be picked up by local 
garbage collectors. Improper propane tank disposal 
might be illegal in some areas. Propane tank disposal 
and filling is a safety issue that is easily handled by a 
propane company.

ATTENTION: Utiliser des contenants de gaz de pétrole 
liquéfié en position appropriée. Les bouteilles de 
propane, les bouteilles de gaz ne seront pas acceptées 
par les éboueurs locaux. L'élimination inappropriée du 
réservoir de propane peut être illégale dans certaines 
régions. L'élimination et le remplissage des bouteilles de 
propane posent un problème de sécurité qui devrait être 
confié à 

une entreprise oeuvrant dans le domaine du 

propane.

Most LP-gas pressure washer heaters are designed to 
operate on LP-gas vapor only. Therefore, all LP-gas 
containers designed for vapor service must be trans-
ported, installed and used in the proper position. Do not 
transport, install or use a vertical cylinder in a horizontal 
or upside down position. Proper care must be taken to 
position a horizontal container in the correct position for 
vapor withdrawal.  Liquid LP-gas could enter the 
system designed for vapor only, possibly creating a 
hazardous condition.
Always use a POL plug installed on a POL valve or a 
dust cap on an ACME/Type 1 valve when transporting 
or storing disconnected containers (full or empty). 
Check for leaks after connecting. Apply approved leak 
detector solution to connection, turn off all burners and 
pilots and open service valve. Leaks will be detected by 
the growth of bubbles. If bubbles grow, tighten or repair 
the connection as needed. Repeat leak test until 
problem is corrected.
Check all tank and the line connections periodically to 
be sure they are tight. When testing for leaks, use 
approved leak detector solution — not matches.

Improved Regulation:

 The second stage regulator 

receives a relatively uniform pressure from the first 
stage regulator. This helps the second stage regulator 
to maintain appliance pressure at a nearly constant 11" 
W.C.

Filling the LP-Gas Container

Only qualified persons should fill your LP-gas 
containers.
CAUTION: Overfilling is hazardous! 

ATTENTION: Le remplissage excessif est dangereux.

DO NOT allow your LP-gas container to be overfilled. 
Stop filling when liquid appears at the fixed level gauge. 
Bleed off excess propane in a safe area. Most LP-gas 
containers are equipped with a fixed liquid level gauge 
which contacts the liquid level at 80% of container 
capacity, allowing 20% for expansion. LP-gas 
containers not equipped with a fixed liquid level gauge 
can only be filled by weight.

In cold climates, in order to keep vaporization of LP-gas 
at the highest level, keep the fuel levels above 50%.

Landa VHG Operator’s Manual  8.913-952.0 - BR

Summary of Contents for VHG

Page 1: ...8 913 952 0 BR 08 21 20 VHG Hot Water Electric Powered Natural Gas or LP Heated Operator s Manual Pressure Washer MODELS VHG4 3000 VHG4 2000 VHG4 2200 VHG5 3000 VHG6 3000 VHG8 3000...

Page 2: ...2 Landa VHG Operator s Manual 8 913 952 0 BR...

Page 3: ...Hot Water Thermostat 24 Pumps 24 Heating Coils 24 Gas Valve Regulator Adjustment 25 Pressure Relief Valve 25 Propane Gas 25 Burner Features 26 Basic Facts 27 Smart Relay Instructions 28 Factory Set P...

Page 4: ...in tenance to keep the machine and its components in good working condition They are listed in this general order Spray Nozzles Unloader Valves Winterizing Procedure Low Pressure Diagnosis High Limit...

Page 5: ...perty damage personal injury or loss of life AVERTISSEMENT Si ces directives ne sont pas suivies la lettre un incendie ou une explosion pourrait survenir et entra ner des dommages la propri t des l si...

Page 6: ...liquides inflammables WARNING Risk of fire Do not change LP tanks when the product is operating or still hot AVERTISSEMENT Risque d incendie Ne pas changer les r servoirs de p trole liquide pendant q...

Page 7: ...in a well ventilated area DANGER Risque d asphyxie Utiliser ce produit uniquement dans un endroit bien ventil 14 Avoid installing machines in small areas or near exhaust fans Adequate oxygen is neede...

Page 8: ...When tightening the POL Nut left hand thread on the service valve draw it up snug with a proper wrench This is a machined male brass fitting which seats securely against a female seat in the POL valve...

Page 9: ...sure Hose Connect one end to water pump high pressure discharge nipple and the other end to spray gun Rupture Disk Secondary pressure release in the unlikely event the unloader valve fails Not Shown U...

Page 10: ...10 Installation VHG 4 5 Landa VHG Operator s Manual 8 913 952 0 BR...

Page 11: ...11 Installation VHG 6 8 Landa VHG Operator s Manual 8 913 952 0 BR...

Page 12: ...t away Allow enough space for servicing the machine Local code will require certain distances from floor and walls Two feet away should be ade quate WARNING Avoid small areas or near exhaust fans AVER...

Page 13: ...reprise oeuvrant dans le domaine du propane Most LP gas pressure washer heaters are designed to operate on LP gas vapor only Therefore all LP gas containers designed for vapor service must be trans po...

Page 14: ...ouble wall type Sometimes vents have to be built of such great length that they come apart at their joints under their own weight These should be screwed together at the joints with sheet metal screws...

Page 15: ...anufacturer and not a licensed contractor and as such we are unable to make recom mendations for suitable make and model of power vents and compliance with local building codes Damper An exhaust stack...

Page 16: ...3 Open the damper to the fully open position 4 Start the pressure washer and allow it to heat up for at least 20 minutes before making any adjust ments 5 Note the values for Excess Air and or Oxygen...

Page 17: ...ne pourrait causer des dommages mat riels ou des blessures corporelles 1 Installation or servicing of gas appliances and controls must only be performed by qualified personnel After installation or se...

Page 18: ...ally grounded Is there ample water supply Have all flammable liquids or gases been removed from installation location Is there adequate gas supply for the BTU rating of the burner Is incoming gas supp...

Page 19: ...ssembly to union on machine and plug in wires STEP 2 Connect the high pressure hose to the discharge fitting Push coupler collar forward until secure STEP 5 Before installing nozzle turn on the water...

Page 20: ...ot water push the burner switch to the ON position and pull the trigger on the spray gun Landa VHG Operator s Manual 8 913 952 0 BR Selection of high or low pressure is accompanied by turning the hand...

Page 21: ...e to the pump Cleaning Tips Pre rinse cleaning surface with fresh water Place detergent suction tube directly into cleaning solution and apply to surface For best results limit your work area to secti...

Page 22: ...detergent valve and spray gun allowing the detergent lines to be flushed and the burner to cool Otherwise coil damage may occur STEP 3 After water has cooled push or turn pump switch to OFF position I...

Page 23: ...etach water supply hose and high pressure hose 3 Turn on the machine for a few seconds until remaining water exits Turn pump off immediately 4 Do not allow high pressure hose to become kinked 5 Store...

Page 24: ...tly to the pump If high pressure is developed in this manner the pump is good and the unloader needs to be repaired or replaced If low pressure is still present then the pump needs repairing CAUTION W...

Page 25: ...rather than rise out of the stack Hence adequate floor space and good ventilation are especially important with propane systems Gas Pressure Requirements All propane fired machines operate on vapor pr...

Page 26: ...union in main burner line below thermostat Slide burner manifold out through shell opening 2 TO CLEAN BURNER JETS Select proper size drill for type gas involved Use pin vise to hold drill and ream ou...

Page 27: ...per Gal Liquid 91 547 102 032 BTU per Lb Liquid 21 591 21 221 Cu Ft per Lb Liquid 8 607 6 53 Cu Ft per Gal Liquid 36 45 31 8 Octane Number 125 91 Molecular Weight 44 09 58 12 To Calculate Running Cost...

Page 28: ...own arrow keys or 8 To set the date repeat steps 6 and 7 9 To accept your entries press OK 10 To go back to the previous menu at anytime press ESC Programming Instructions The 900 1400 can be configur...

Page 29: ...indow shows the three parame ters See figure 4 NOTE Ta is the accumulator timer and T is the adjustable timer the variable that changes 5 Press OK to change the value of Timer 1 Using the left right a...

Page 30: ...e Pump On switch Timer 2 30 00 Seconds Pump will run in bypass for 30 seconds before shutting off machine is still in standby mode Pulling the gun trigger will restart the pump Timer 3 15 00 Seconds I...

Page 31: ...s for 3 minutes and shut off To restart push the Pump On switch Timer 2 01 00 Hours To operate in time delay mode timer 2 must be deactivated This is done by setting timer 2 to value greater than time...

Page 32: ...lumn 6 35 oz sq in 11 Water Column 4 lb sq in 1 lb sq in 27 71 Water Column 1 lb sq in 14 73 lbs sq in 1 Mercury 39 lb sq in 1 Std Atmosphere 14 73 lbs sq in Date Oil Changed Month Day Year Estimated...

Page 33: ...er severe conditions Maintenance Schedule Replace Fuel Lines Annually Pump Oil SAE 10W 40 non foaming Inspect Daily inspect the oil level Change After first 50 hours then every 500 hours or annually C...

Page 34: ...iscosity of detergent Dilute detergent to specifications Restriction behind float tank screen removed Install restriction Hole in detergent line s Repair hole Strainer basket plugged Remove and clean...

Page 35: ...g kit Fouled or dirty inlet or discharge valves in pump Clean inlet and discharge valve Worn inlet or discharge valves Replace with valve kit Obstruction in spray nozzle Remove obstruction Leaking pre...

Page 36: ...is turned on 2 With gas on and system sparking probe terminals PV and 24V GND If pilot gas does not flow with 24 volts at these terminals replace gas valve 3 Probe terminals PV and MV PV If 24 volts...

Page 37: ...r rod the main burner should turn on If it does not replace the ignition control unit SHORT CYCLING OF MAIN BURNER MAIN BURNER TURNS OFF BEFORE THE BURNER SWITCH OR FLOW SWITCH IS TURNED OFF Draft con...