Monitor the indicated temperature on the thermostat and ensure temperature reduces to the set
point.
While the refrigeration system is operating, monitor the evaporator suction line temperature via
the probe 2 by pressing and holding the Arrow down button. Record the lowest temperature and
then set the AF parameter 9°F below this reading. This will ensure protection of the HX plate
and refrigeration system in the event of a pump failure or freeze up.
NOTE:
1.
The thermostat has a minimum compressor “OFF” time of 3 minutes to prevent short cycling.
Temperature & differential settings should be such that the number of compressor starts does
not exceed the manufacturers recommendations.
2. The Thermostat will not be energised unless the refrigeration control switch is turned on.