Siberian Elite Glycol Chiller 220V / 60Hz
www.lancerbeverage.com
Page 10 of 17
Hoshizaki Lancer reserve the right to change specifications without notice
Part No: 68000205
Images are for illustration purposes only as product may vary.
No 016
– 12 February 2016
6.2
Programming Instructions
6.2.1
Set Point
Push and hold the “SET” key, “st” is displayed then the current set point is displayed and
flashes, release “SET” key to change the set point value.
Push the “UP” or “DOWN” arrow keys to change the set point value.
To accept the new value press the “SET” key or wait 60 seconds without pressing any keys
for the unit to time out.
6.2.2
Other Parameters
Push and hold the “SET” key, until “rd” is displayed.
Select the required parameter to change using the “UP or “DOWN arrow keys then
press the “SET” key to display its value.
Press the “UP” or “DOWN” key to change its value.
Press the “SET” key to store the new value and move to the next parameter.
To exit from programming mode press the “SET” key for 3 seconds or wait 60 seconds
without pressing any keys for the unit to time out.
6.2.3
Eco Mode
In the ECO m
ode an offset is added to the Set point: “St” + “r4”.
To set the ECO mode press and hold the “UP” key, “on” or “oF” is displayed showing how
ECO mode will be changed, when “on” or “oF” disappears release key. In ECO mode “Ec”
is displayed alternated to probe 1, Glycol temperature actual value.
6.3
Alarm Signals
When an alarm is activated, the display shows the corresponding message that flashes alternating
with the temperature.
Message
Cause
Reset
“E0”
Glycol Probe Failure
Automatic
“E1”
Refrigeration Line Probe Failure
Automatic
“LO”
Low Temperature Alarm
Automatic
“HI”
High Temperature Alarm
Automatic
“AF”
Antifreeze Alarm
Manual
Antifreeze alarm can be reset by holding “UP” and
“DOWN” keys for 5 seconds.