Warning
To avoid possible fatal electric shock or serious injury the
Superchiller must be electrically grounded.
Electrical Connection Must Be Made In Accordance With The
Appropriate Local Codes And Regulations.
Use of an RCD is recommended.
6.10
Plumbing the drain and CO2 exhaust
The 19mm overflow drain tube exiting from the RH Pump Panel of the unit should be plumbed to a
suitable drain, installation in accordance with AS/NZS 3500.1 and AS/NZS 3500.2.
The 6mm barb labelled as CO
2
EXHAUST should be plumbed to an outside safe area.
6.11
Commissioning
Unplug carbonator and recirculation pumps power supply leads from electrical box located
under lid.
Connect Superchiller power supply lead to an appropriate 3 pin socket outlet and switch on.
Compressors, condenser fans and agitator motors should all operate.
When Superchiller ice bank is fully formed (approx. 4 hours) the compressors and condenser
fans will cycle off, but agitator will run continuously (unit has cycled off).
After Superchiller has cycled off, reconnect carbonator and recirculation pumps.
6.12
Purge System
Progressively activate each dispensing valve or Bargun connected to the Superchiller systems until
an uninterrupted flow of soda, water (where applicable), and syrup pours from each dispenser.
7. Scheduled Maintenance
Warning
The Chillers must not be cleaned by a water jet.
The following Superchiller routine maintenance should be performed at the intervals listed.
Daily
Cleaning/Sanitising
The Superchiller supplies soda water to the dispensing valves/barguns. To ensure optimum drink quality and
system performance at all times please follow cleaning and sanitising procedures for the dispensing
valves/barguns recommended by the valve/bargun manufacturer.