background image

3

INSTALLATION

Unpack the Dispenser

1.  The Lancer dispenser is shipped in a corrugated shipping 

carton.

2.  Remove dispenser from corrugated shipping carton.

Tower Installation

1.  Route appropriate tubing from the water source to the plain 

water inlet at tower and connect tubing to inlet using the 

oetiker pliers and fittings,(see Plumbing Diagram on unit or 

page 11 for reference).

 

Inspect unit for concealed damage. If evident, notify 

 

delivering carrier and file a claim against the same.

NOTE

Selecting/Preparing Counter Location

1.  Select a level, well ventilated location that is in close       

proximity to a properly grounded electrical outlet, within five 

(5) feet (1.5 m) of a drain, a water supply that meets the 

requirements shown in the Specifications section found on 

page 2, and away from direct sunlight or overhead lighting. 

2.  The dispenser is designed to be installed permanently to 

a counter and must be sealed with a bead of clear silicone 

caulk or sealant which provides a smooth and easily  

cleanable bond to the counter.

 

The dispenser should only be installed in a location 

where it can be overseen by trained personnel

NOTE

 

NSF listed units must be sealed to the counter or have 

four (4) inch legs installed.

NOTE

 

To assure that beverage service is accessible to all 

customers, Lancer recommends that counter height 

and equipment selection be planned carefully. The 

2010 ADA Standards for Accessible Design states that 

the maximum reach height from the floor should be no 

more than 48” if touch point is less than 10” from the 

front of the counter, or a maximum of 46” if the touch 

point is more than 10” and less than 27” from the front 

of the counter. For more information about the 

 

customer’s legal requirements for the accessibility of 

installed equipment, refer to 2010 ADA Standards for 

Accessible Design - http://www.ada.gov.

NOTE

In order to facilitate proper dispenser drainage, ensure 

that the dispenser is level, front to back and side to 

side. Place a level on the top of the rear edge of the  

dispenser. The bubble must settle between the level 

lines. Repeat this procedure for the remaining three 

sides. Level unit if necessary. For optimum perfor-

mance place the unit at a 0° tilt. The maximum tilt is 5°.

Leveling the Dispenser:

3.  Select a location for the remote chiller systerm, syrup 

pumps, CO

2

 tank, syrup containers, and water filter  

(recommended).                                                                                  

4.  Cut out required opening in counter for the water/soda and 

syrup lines in the designated dispenser location.

 

Unit is designed to be supported by a remote chiller 

 

system or remote ice cooled system. Please see the 

manufacturer’s specifications and instructions for 

 installation.

NOTE

6.  Connect drain line to fitting at the bottom of the drip tray and 

route to designated open type foor drain.

A

B

C

A. Oetiker Pliers

B. Fitting

C. Tubing

D. Syrup/Water 

     Inlet

D

 

DO NOT PLUG UNIT INTO GROUNDED ELECTRICAL 

OUTLET AT THIS TIME. 

Make sure that all water lines 

are tight and unit is dry before making any electrical 

connections

WARNING

4.  Route appropriate tubing from the syrup pump location to the 

syrup inlets and connect tubing to inlet. Repeat for remaining 

syrup lines 

5.  Route the power supply cord to a grounded electrical outlet 

of the proper voltage and amperage rating.

 

Drain line must be insulated with a closed cell 

 

insulation. Insulation must cover the entire length of 

the drain hose, including fittings. The drain should be 

installed in such a manner that water does not collect 

 

in sags or other low points, as condensation will form.

CAUTION

 

Pouring hot water down the drain may cause the Drain 

 

Tube to collapse. Allow only luke warm or cold water to 

 

enter the Drain Tube.

 

Pouring coffee, tea, or other 

 

similar substances down the drain may cause the Drain 

 

Tube to become clogged.

ATTENTION

2.  Connect tubing to water source then flush water line to check 

for leaks.

3.  Route appropriate tubing from the remote chiller system 

location to the carbonated water inlet on tower and connect 

tubing to inlet.

Summary of Contents for Multi-Valve Unit Tower

Page 1: ...for the unit being installed is required or needed please refer to the Lancer web site lancercorp com for immediate access or for your convenience scan this QR code with a mobile device app required...

Page 2: ...25 inches 184 15 mm Depth 9 inches 228 6 mm Height 16 5 inches 419 mm WEIGHT Shipping 15 lbs 7 0 kg CARBON DIOXIDE CO2 SUPPLY Min Pressure 70 PSIG 0 483 MPA Max Pressure 80 PSIG 0 552 MPA FITTINGS Pl...

Page 3: ...inage ensure that the dispenser is level front to back and side to side Place a level on the top of the rear edge of the dispenser The bubble must settle between the level lines Repeat this procedure...

Page 4: ...URN ON CO2 SUPPLY AT THIS TIME WARNING 7 Repeat Step 6 for both low pressure CO2 regulators on the regulator manifold routed to the unit and the syrup pumps A CO2 Regulator B Screwdriver C Regulator A...

Page 5: ...turning on CO2 7 Turn on CO2 at the source then using a screwdriver adjust the high pressure regulator at the source to 110 PSI 0 758 MPA then tighten locknut with wrench MULTI VALVE UNIT MVU PROGRAMM...

Page 6: ...positions B C D E and F 5 Press the Pour Cancel to save the changes and exit the programming mode Set MVU for Flavor Shots Refer to Overview Illustration for touch pad reference NOTE The Shot button w...

Page 7: ...press a brand button 5 Press the brand button again to pour for 4 seconds 6 Check for 10 oz of water in the ratio cup 7 Repeat process for other water type 8 Press Pour Cancel to exit programming mod...

Page 8: ...d for shot mode the LED light on that brand will blink twice and turn off NOTE The XL LED will blink slowly to indicate that it has been programmed The other size buttons are automatically set and do...

Page 9: ...p lines with BIB connectors in a bucket of warm water 3 Activate each valve to fill the lines with warm water and flush out syrup remaining in the lines 4 Prepare Cleaning Solution described on previo...

Page 10: ...ature too high 2 CO2 pressure too high 3 Water flow rate too high 4 Nozzle and diffuser not installed 5 Nozzle and diffuser not clean 6 Air in BIB lines 7 Poor quality ice 1 Correct prior to dispenser...

Page 11: ...or outlet line 2 Defective BIB pump check valve 1 Replace line 2 Replace BIB pump BIB pump continues to operate when bag is empty 1 Leak in suction line 2 Leaking o ring on pump inlet fitting 1 Replac...

Page 12: ...12 ILLUSTRATIONS PART LISTINGS MVU Tower Assembly...

Page 13: ...775 01 Retainer Slide 26 04 0481 Scr 8 32x1 125 27 64 5011 02 PCB Assy 28 49 0330 Nozzle Assy 49 0331 Nozzle Assy Flavor Shots Only 29 05 2687 01 Plate Nozzle 30 05 2682 Bracket Cover 31 54 0464 Cover...

Page 14: ...14 Wiring Diagram...

Page 15: ...15 Soda Water Flow Controls and Solenoids Plumbing Diagram...

Page 16: ...Lancer Corp 800 729 1500 Technical Support Warranty 800 729 1550 custserv lancercorp com lancercorp com...

Reviews: