2
PUSH
I C E
SUFFICIENT CLEARANCE
FOR
34" (864 mm)
30 1/2" (775 Mm)
AIR
OUT
AIR
OUT
AIR
OUT
AIR
OUT
9 3/4" (248 Mm)
MINIMUM
of 6" (152 mm)
AIR
IN
AIR
IN
6" (152 mm) clearance
6" (152 mm) clearance
22" (559 mm)
MINIMUM
of 6" (152 mm)
34" (864 mm)
30 1/2" (775 mm)
DISPENSE HEIGHT
FILLING MANUALLY WITH ICE,
WHEN ICE MAKER NOT USED
clearance above ice maker
MINIMUM
of 6" (152 mm)
clearance above ice maker
wall clearance
Figure 1
C. Location must insure sufficient clearance on sides, top and back of unit is provided for
ventilation and air circulation (see Figure 1).
D. Additionally, if an ice maker is not top mounted on the unit, sufficient clearance should be
provided [a minimum of 16 inches (406 mm) is recommended] to allow filling the unit with ice
1.
If at all possible, location should be away from direct sunlight or other heat sources.
2.
Connecting lines may be run through access in back of the unit or extend down through a
counter cut out.
3.
The counter must support the weight of the dispenser, ice, and possibly an ice maker. Total
weight may exceed 800 pounds (363.6 kg).
B. Unit may be installed directly on the countertop or on legs supplied with the unit. If installed
directly on the counter, the unit must be sealed to the countertop.
If an ice maker is to be
mounted on top of dispenser, do not install dispenser on legs.
NOTE
Water pipe connections and fixtures directly connected to a potable water supply must all be
sized, installed, and maintained according to Federal, State, and Local laws.
The water supply
must
be protected by means of an air gap, a backflow prevention device
(located upstream of the CO
2
injection system) or another approved method to comply with
NSF standards. A backflow prevention device must comply with ASSE and local standards.
It is the responsibility of the installer to ensure compliance.
NOTE:
Please refer to specific icemaker
model for proper air intake/exhaust
ventilation with Lancer units.