PAGE 7

Do not add salt to the brine tank yet. Do not plug the transformer into the receptacle yet. Make sure inlet and outlet valves are to their 

closed positions. If using optional bypass, place in bypass position. Turn on main water supply. Open a cold water faucet. This will clear 

the line of any debris (solder, pipe dope, etc.) that may be in the line. Let water run at faucet for a couple minutes, or until clear. Turn 

off faucet. Manually add 1 ½  gallons of water to the brine tank. Now plug the transformer into a 120 volt receptacle (be certain the 

receptacle is uninterrupted). Within 5 seconds the control display and buttons will illuminate and the time of day screen will appear.

• 

 Press and hold the 

REGEN

 button for approximately 5 seconds until the motor starts.

• 

 Wait until display reads 

FILL

 and numbers start counting down.

• 

 Momentarily press 

REGEN

 again. Valve is now in the 

SOFTENING

 position.

• 

 Momentarily press 

REGEN

 again. Valve is now in the 

BACKWASH 

position.

• 

 Momentarily press 

REGEN

 again. Valve is now in the 

REGENERANT DRAW

 position.

• 

Momentarily press 

REGEN

 again. Valve is now in the 

AIR RELEASE 

position.

• 

 Momentarily press 

REGEN

 again. Valve is  now in the second 

BACKWASH 

position.

If using optional bypass 

SLOWLY

 turn bypass valve to 

DIAGNOSTIC

 position (

See figure 3 on page 4

) or slowly open inlet valve to 

allow water to slowly enter the Conditioner.

When water is flowing steadily to drain without the presence of air, momentarily press 

REGEN

 

again. Display will read 

RINSE

. Open 

the outlet valve of the conditioner, or if using optional bypass place to 

NORMAL OPERATION  MODE

 (

see figure 1 on 

page  4

). Allow control to finish the 

RINSE 

cycle. Allow the control to automatically advance to the 

SOFTENING

 position. 

Now load the brine tank with salt. Solar Salt is recommended. The brine tank salt level should be checked every couple of 

weeks to determine salt usage. Keeping the brine tank salt level at least 1/2 full is recommended.

SANITIZING:

 Use 2 oz. of 5 ¼% unscented household chlorine bleach for each cubic foot of resin. Pour bleach directly into the 4” 

diameter white brine well located inside the brine tank. Press and hold the 

REGEN

 for 5 - 6 seconds until the motor starts running. Allow 

system to complete the regeneration automatically. Check for other local and state codes which may also specify sanitation methods.

Note: The first step of the regeneration process is to fill the brine tank with the proper amount of water. The brine tank will 

only have a very slight amount of water in it after the regeneration cycles are completed.

PLACING THE CITY SOFT PLUS INTO SERVICE

GENERAL OPERATION

User Displays

When the system is in normal service mode, one of up to five 

available User Displays will be shown. Pressing 

NEXT

 will 

alternate between the following displays:

 

• Current time of day

 

• Treated water flow rate

 

• Service contact name and phone number (if entered)

 

• Remaining Capacity of treated water available

 

• Remaining days to regeneration (if Day Override is

    

programmed)

Pressing the 

 button while in the Capacity Remaining or 

Days Remaining displays will decrease the capacity remaining 

in ten gallon increments or the days remaining in one day 

increments. 

To clear the Service Call reminder

, press the 

 and 

  

buttons simultaneously while the number and banner text 

screen is displayed.

If the system has called for a regeneration that will occur at 

the preset time of regeneration, the words REGEN TODAY will 

alternate with the header on the display. 

Utilizing the control valve’s built-in water meter, a water drop 

flashes on the display when water is being treated (i.e. water is 

flowing through the system).

Drop will flash while water 

is being treated.

NEXT

NEXT

NEXT

Contact Screen

NEXT

Note: As an energy saving feature, the control will automatically turn off all SOLID BLUE or SOLID GREEN display 

illumination and keypad illumination after about 5 minutes of the last keypad button push. Any further keypad touch will 

cause the re-illumination of the display and keypad, and re-activate keypad control.

Summary of Contents for City Soft Plus XFactor Series

Page 1: ...free service When installed in accordance with the following instructions and if given reasonable care clear soft water will be the result For servicing and future inspection purposes please file this...

Page 2: ...Total Gallons Per Day x Grains Per Gallon of hardness Total Grains per Day INSTALLATION DATE SERIAL NUMBER INSTALLER NAME PHONE ADDRESS TABLE OF CONTENTS Job Specifications 2 Pre Installation Review...

Page 3: ...r treating water that is microbiologically unsafe or of unknown quality without adequate disinfection before or after treatment GENERAL INSTALLATION AND SERVICE WARNINGS PRE INSTALLATION REVIEW WATER...

Page 4: ...rs are glass filled Noryl or equivalent and the nuts and caps are glass filled polypropylene All seals are self lubricating EPDM to help prevent valve seizing after long periods of non use Internal o...

Page 5: ...pes that are connected on the drain line control fitting Failure to do this could cause interior damage to the drain line flow control fitting Never insert a drain line into a drain sewer line or trap...

Page 6: ...WITH BRINE TANK OVERFLOW GRAVITY DRAIN ONLY USED IN CASE OF MALFUNCTION IN THE BRINE SHUTOFF DO NOT CONNECT TO CONTROL VALVE DRAIN LINE IF UNIT IS INSTALLED WHERE OVERFLOW COULD CAUSE WATER DAMAGE CO...

Page 7: ...least 1 2 full is recommended SANITIZING Use 2 oz of 5 unscented household chlorine bleach for each cubic foot of resin Pour bleach directly into the 4 diameter white brine well located inside the br...

Page 8: ...Set the amount of hardness in grains of hardness as calcium carbonate per gallon using the or buttons The default is 20 with value ranges from 1 to 150 in 1 grain increments Note The grains per gallon...

Page 9: ...rn to previous digit Banner Text Set the banner text up to a maximum of 44 characters Use the or to select letters of the alphabet numbers ampersand or a space in the banner text Press NEXT to forward...

Page 10: ...Adaptor Input Voltage Hertz 120V AC 60 Hz AC Adaptor Output Voltage Current 12V AC 500 mA 3 Volt Lithium Coin Cell Battery type 2032 PC Board Relay Terminal Block DC Output Voltage 12V DC Relay Speci...

Page 11: ...SDCS 1 A8056 Centaur Carbon for chloramine reduction in 7 LESDCS 1 6 A4074 3 4 Cu Ft 39 LBS Ion Exchange Resin for Model 7 LXD 75 1 A4074 1 Cu Ft 52 LBS Ion Exchange Resin for Model 7 LXD 100 1 A4074...

Page 12: ...sh down to fully seat Battery replacement is 3 volt lithium coin cell type 2032 Correct Battery Orientation 1 2 3 5 6 4 X FACTOR FRONT COVER AND DRIVE ASSEMBLY After completing any valve maintenance i...

Page 13: ...etailed service instructions 1 2 3 4 5 INJECTOR CAP INJECTOR SCREEN INJECTOR PLUG AND O RING Drawing No Order No Description Qty 1 V3005 Spacer Stack Assembly 1 2 V3004 Drive Cap Assy 1 3 V3178LP Back...

Page 14: ...RITICAL OR HEALTH EFFECT APPLICATIONS The nut and caps are designed to be unscrewed or tightened by hand or with the service spanner wrench see page 16 If necessary a pliers can be used to unscrew the...

Page 15: ...wing No Order No Description Quantity 1 V3151 Nut 1 Quick Connect 2 2 V3150 Split Ring 2 3 V3105 O Ring 215 2 4 V3191 Vertical Adapter 2 INSTALLATION FITTING ASSEMBLIES 4 Water Flow Proper DLFC orient...

Page 16: ...2 8 V3152 O ring 135 2 9 V3155 O ring 112 2 10 V3156 O ring 214 2 BYPASS VALVE Order No V3193 Although no tools are necessary to assemble or disassemble the valve the wrench shown in various position...

Page 17: ...antity of 24 Order No V3007 09 Description Fitting 1 1 Brass Sweat Assembly Drawing No Order No Description Quantity 1 V3151 Nut 1 Quick Connect 2 2 V3150 Split Ring 2 3 V3105 O Ring 215 2 4 V3375 Fit...

Page 18: ...are not fully engaged the piston rod is not in hole the wires are jammed between the drive bracket and drive back plate or the gear is not engaging the drive cap assembly To inspect the drive gears t...

Page 19: ...embly and hand tighten the drive cap assembly Continue to tighten the drive cap assembly using a screwdriver as a ratchet until the black o ring on the spacer stack assembly is no longer visible throu...

Page 20: ...used Sharp objects which can score the plastic should not be used to clean the injector Scoring the injector or increasing the diameter of the hole could change the operating parameters of the inject...

Page 21: ...eter f Defective PC Board f Replace PC Board 4 Control valve regenerates at wrong time of day a Power outage a Reset time of day If PC Board has battery back up present the battery may be depleted See...

Page 22: ...possible increase pump switch cut in to 25 psi b Incorrect injector size b Replace injector with correct size for the application c Restricted drain line c Check drain line for restrictions or debris...

Page 23: ...NEXT and REGEN buttons for 3 seconds to resynchronize software with piston position or disconnect power supply from PC Board for 5 seconds and then reconnect c Main drive gear too tight c Loosen main...

Page 24: ...reconnect c MAV NHBP motor not fully engaged with reduction gears c Properly insert motor into casing do not force into casing Press NEXT and REGEN buttons for 3 seconds to resynchronize software wit...

Page 25: ...PAGE 25 NOTES...

Page 26: ...PAGE 26 A DIVISION OF C B TOOL CO 1340 MANHEIM PIKE LANCASTER PA 17601 3196 TEL 717 397 3521 FAX 717 392 0266 www lancasterwatertreatment com E mail info lancasterpump com 4 14...

Reviews: