24
5
Firing Rate Controller (optional)
5
Firing Rate Controller (optional)
5.1
Operation
5.1.1
Enter Setpoint of Firing Rate Controller
Up to software version A3i1023, you can change the setpoint through parameter setting.
From software version A3i1023 onwards, you can change the setpoint of the firing rate con-
troller. This function works for running burner.
-display on firing rate rating
NOTICE
If you change the setpoint, the switchpoints will be shifted because thay are defined as differ-
ence value to the setpoint.
NOTICE
Should the option ’Control by Atmospheric Conditions’ be active, the setpoint cannot be
changed and saved via the front plate. These setpoints can only be changed by the PC Re-
mote Software (DLT1040) or with the GKI300 (DLT7106).
5.1.2
Operating Description
The burner start-up is carried out as described above. At least ’Burner ON’ signal and ’Re-
lease’ must be sent by firing rate controller.
The burner starts as soon as it is receiving signals ’Burner ON’ and ’Release’ from firing rate
controller. The firing rate controller is in operation not before the burner is running and the sig-
nal ’Control Release’ is pending.
The default value of firing rate for fuel/air ratio control is set via integral firing rate controller.
Depending on the difference between actual and setpoint value and adjusted control param-
eters this default firing rate value is set. When actual value is exceeding to maximum value
the firing rate controller switches OFF combustion.
The firing rate controller is active in AUTOMATIC mode only.
Switch (4) channel 3 downwards and channel 4
upwards simultaneously.
The display shows the entry field for setpoint.
You can change the setpoint through (4) channel 2.
With the ENTER key (3), you can save the new value.
Switch (4) channel 3 downwards and channel 4
upwards simultaneously
Leave the mode without saving the setpoint.
Summary of Contents for VMS Series
Page 2: ......
Page 119: ...118 10 Appendix...
Page 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Page 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Page 142: ...141 10 Appendix...
Page 143: ...142 10 Appendix 10 15 Protocol Example...
Page 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Page 145: ...144 10 Appendix...