Commissioning
The O
2
values calculated during burner adjustment are input and stored as follows, regardless
of whether the burner is off or in operation. The O
2
target values can be input arbitrarily. It is
not necessary to observe any particular sequence.
Fig. 6-6 Typical O
2
target value curve
NOTICE
The O
2
target values can only be stored in the programmed firing rate points. If firing rate
points are skipped, the line in between is interpolated.
–
Switch (1) to target value.
–
Channel key 4 (4) is used to set the required O
2
target value.
–
Press the Enter key (3).
NOTICE
Each stored O
2
target value can be changed as many times as necessary, including immedi-
ately after storing it.
Switch (3) to firing rate and
use channel key 1 (5) to call up the next firing rate point;
etc.
As soon as all required O
2
target values have been entered,
switch (2) back to Automatic.
.The O
2
target value curve is now stored.
Turn selector switch (2) to O
2
TRIM
Delete the whole O
2
curve with channel key 4 (4)
upwards.
If only points need to be changed, push channel key 4
(4) downwards.
Turn selector switch (1) to FIRING RATE RATING (firing
rate).
Using channel key 1 (5), the composite curve's pro-
grammed firing rate points can now be called up.
Summary of Contents for VMS Series
Page 2: ......
Page 119: ...118 10 Appendix...
Page 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Page 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Page 142: ...141 10 Appendix...
Page 143: ...142 10 Appendix 10 15 Protocol Example...
Page 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Page 145: ...144 10 Appendix...