LAMINOX Idro TERMOBOILER Mini Series Instructions For Installation, Use And Maintenance Manual Download Page 38

38 

 

EACH ALARM CONDITION CAUSES IMMEDIATE BOILER SHUTDOWN 
To exit from an alarm condition, always press button "4" until the message "FINAL 

CLEANING" appears. 

You will also need to take additional steps, depending on the type of alarm generated 

If you do not exit from the alarm condition within a given time (a few hours), the alarm will be sent 

into boiler memory and the display will show the message "ALARM MEMORY". To exit from this 

condition, press button "4" as per above. 

 

AL 1 - Black-out 

This alarm is activated when the boiler is disconnected from the mains. 

What to do 

Put the boiler in stand-by by pressing the off button for a few seconds. 

AL 2 - Smoke sensor 

This alarm signals breakage of the smoke sensor 

What to do 

 Put the boiler in stand-by by pressing the off button for a few seconds (4). 

 Wait and make sure that the combustion of pellets left in the brazier has been completed. 

 If necessary, call a support centre to replace the sensor 

AL 3 - Smoke temp 

This alarm signals excessive smoke exhaust temperature (see safety devices) 

What to do 

 Put the boiler in stand-by by pressing the off button for a few seconds (4). 

 Wait and make sure that the combustion of pellets left in the brazier has been completed. 

 If necessary, call a support centre to replace the sensor 

AL 4 - Extract fault 

This alarm indicates a failure to read the revs of the smoke expulsion motor by the control board. 

It may have been activated due to motor fault or due to a lack of connection between the rev 

reader (encoder) in the motor and the board. 

What to do 

Put the boiler in stand-by by pressing the off button for a few seconds. 

Try switching the boiler back on. 

Contact your support centre if the problem persists. 
AL 5 – No start 

This alarm signals an ignition failure. This alarm is activated when, during the  start-up phase, a 

maximum waiting time (about 20 minutes) is exceeded without the machine switching on 

successfully. (

see ignition

AL 6 – No pellet 

This alarm indicates a flame failure in the brazier during normal boiler operation. The main causes 

are: no pellets in the tank or blocking of the pellet feed screw. 

What to do 

 Put the boiler in stand-by by pressing the off button for a few seconds. 

 Empty the brazier of all unburned accumulated pellets. 

 In the event of pellet exhaustion in the tank, refuel the boiler and ignite it again. Do not insert 

pellets until the boiler has cooled completely. 

Pellet refilling must always be performed with 

the boiler off 

or with the boiler operating with the flame present. 

 In the case of a pellet feed screw block, empty the tank and remove any foreign bodies present 

in the feed screw. Then refill with pellets and start the boiler back up 

 

In the case of repeated feed screw blocks, call a support centre 

Summary of Contents for Idro TERMOBOILER Mini Series

Page 1: ...al is an integral part of the product Laminox S r l reserves the right to change the characteristics and data reported in the following document at any time and without warning in order to improve the...

Page 2: ...ation N1 but airtight at a pressure up to 0 2 mbar Refer to standard UNI 10683 2012 B Install a 1 anti condensation valve with 55 C opening C Connect the room programmable thermostat to the external t...

Page 3: ...t the boiler to the mains only after proper professional connection to the chimney flue The power cable plug must remain accessible after installation of the boiler Only operate the boiler with regula...

Page 4: ...m 10 3 FUEL 11 4 1 General notes 12 4 INSTALLATION 12 4 2 Minimum safety distances 13 4 3 Flooring protection 15 4 4 Minimum distances for positioning air intake vents 15 4 5 Fume exhaust duct 16 5 1...

Page 5: ...stion chamber cleaning 40 9 5 Smoke chamber cleaning 41 9 6 Exhaust system cleaning 41 9 7 Cleaning metal and ceramic parts 41 9 8 Cleaning the glass 41 9 9 Glass breakage 41 9 10 Replacing the remote...

Page 6: ...than 45 fig 2 Each device must have its own chimney flue with a section equal to or greater than the diameter of the fume exhaust pipe of the boiler and a height no less than the one stated Never use...

Page 7: ...s to prevent penetration into the flue of rain snow or foreign bodies and so that in the event of winds in any direction and at any angle it assures the discharge of combustion products wind proof chi...

Page 8: ...ction device The room adjacent to the permanent openings must meet the requirements set out in the paragraphs above The adjacent room cannot be used as a garage for storage of combustible material or...

Page 9: ...W 17 2 kW Performance 90 8 90 6 90 1 Suggested damper 10 12 Pa 10 12 Pa 10 12 Pa Pellet tank capacity 40 Kg 40 Kg 40 Kg Power consumption 480 W 480 W 480 W Smokes outlet diameter 80 mm 80 mm 80 mm Wei...

Page 10: ...10 2 5 Wiring diagram...

Page 11: ...hat described by the manufacturer AVOID using low quality pellets or pellets containing dispersed sawdust powder resins or chemicals additives or adhesives AVOID using moist pellets The use of unsuita...

Page 12: ...e installed in a technical room It is forbidden to install them in open verandas or outdoors Installation in rooms containing other generators that collect air from the environment is prohibited par 6...

Page 13: ...st always be guaranteed 4 2 1 Corner installation mm 4 2 2 Wall installation mm Safety distances from flammable material Minimum distance in air from the flammable rear wall P 500 mm Minimum distance...

Page 14: ...Distance from flammable ceilings and false ceilings mm Minimum mandatory distance from flammable material and from roof for maintenance H 800 mm 4 2 4 Distance of fume exhaust system from flammable w...

Page 15: ...positioning air intake vents Pellet boiler combustion air intake vents cannot be connected to an air distribution system or directly to a wall mounted air intake vent Correct and safe positioning of t...

Page 16: ...here exhausted flue gas or vapours from other equipment boilers hoods etc is prohibited 4 5 2 Tubes and maximum usable lengths All the components must be made of material with A1 fire reaction class U...

Page 17: ...hich is flammable or has flammable parts 100 280 Concrete wall or roof 50 180 Brick wall or roof 30 140 4 5 4 Using a traditional type chimney flue If you wish to use an already existing chimney flue...

Page 18: ...ecured to the building fig 13 must be used An inspection area must be created at the base of the duct for performing periodic checks and maintenance The duct must be equipped with a wind proof chimney...

Page 19: ...ck the product being careful not to damage or scratch it Remove the accessory package and any pieces of polystyrene or cardboard used to block removable parts etc from the boiler furnace Also remember...

Page 20: ...compatibility with the machine specifications During installation and operation take into account that disposal of the minimum power delivered by the machine must be ensured Make sure that the thermal...

Page 21: ...18 Magnesium anode 19 Jolly valve Caution to prevent the heating system from having to be regularly cleaned it is best to install a magnetic sludge remover this filter aids routine maintenance increas...

Page 22: ...inerator or in any other way other than that for which it was designed Do not use liquid fuels Do not make any unauthorised modifications to the device Only use original replacement parts recommended...

Page 23: ...rmation about boiler operating status Access the menu to view various types of displays and adjust the settings available depending on the level of access Depending on the operating mode the displays...

Page 24: ...ilure to install incorrect first ignition or improper use Make sure that electrical and plumbing connections have been performed properly Also check that the hydraulic system has a sufficient expansio...

Page 25: ...or a variable time interval depending on the model and pellets begin to fall inside the brazier Remember that the brazier must be perfectly clean at this beginning of this stage Once this pre loading...

Page 26: ...ormation The first line shows the time On the second line to the right the temperature of the water in the boiler appears The third line shows the message WORKING with the set power from 1 to 5 to the...

Page 27: ...ceeding the set temperature by 8 C the boiler goes in standby mode The display will show WAITING FOR COOL during the final cleaning phase and then ECO STOP during the standby mode 6 3 5 Circulator Thi...

Page 28: ...ing button 4 for a few seconds Once the shutdown signal has been received the display will show the FINAL CLEANING message and the fume exhaust fan will continue to run at full speed for a minimum tim...

Page 29: ...mperature setting mode In temperature setting mode it reduces the set value In technical parameter setting mode it reduces the set value In work mode it activates room temperature setting BUTTON 3 Swi...

Page 30: ...which you are located Use buttons 1 and 2 to modify a parameter value temperature time etc Use buttons 5 and 6 to move horizontally between different menus or sub menus or different parameters 7 1 MEN...

Page 31: ...which days of the week they must be active Weekend program 2 start ups and shutdowns valid only for Saturday and Sunday Below is the diagram of the various Menu levels Access the menu by pressing 3 re...

Page 32: ...3 Menu 3 3 WEEKLY PROG The weekly programming group includes 4 start ups and 4 shutdowns For each on off pair you can decide which day of the week to activate the corresponding pair controls The first...

Page 33: ...00 00 23 50 OFF M 3 3 12 STOP PROG 2 Off time 00 00 23 50 OFF M 3 3 13 MONDAY PROG 2 reference day on off M 3 3 14 TUESDAY PROG 2 on off M 3 3 15 WEDNES PROG 2 on off M 3 3 16 THURSDAY PROG 2 on off M...

Page 34: ...ons for the weekend Saturday and Sunday As per daily programmes we have an enabling parameter and 2 pairs of start up and shutdown times Programming will be active as stated only on Saturday and Sunda...

Page 35: ...ion are available This menu is for qualified service personnel use 7 8 Menu 09 TECHNICAL CALIBRATIONS This menu is protected by an access key and is intended for qualified service personnel 7 9 Menu 1...

Page 36: ...nts in the exhaust tube negligent maintenance adverse weather conditions such as persistent wind etc If the boiler flue gas pass contains an accumulation of ash that obstructs the normal passage of th...

Page 37: ...ssage modulate At the same time if despite passage to modulation the water temperature continues to increase and exceeds the second pre set safety limit about 90 C the boiler will pass into alarm mode...

Page 38: ...or AL 4 Extract fault This alarm indicates a failure to read the revs of the smoke expulsion motor by the control board It may have been activated due to motor fault or due to a lack of connection bet...

Page 39: ...the boiler by pressing the ON OFF button 4 In the event of a repeated alarm call the support centre AL 9 Water sensor This alarm is activated by the breakage or disconnection of the water probe of the...

Page 40: ...razier cleaning When the flame becomes red or is weak accompanied by black smoke it may mean that there are ash deposits or incrustations which are not allowing correct boiler operation and which must...

Page 41: ...until it cools down Do not use any material that can scratch or damage theglass 9 9 Glass breakage The boiler is equipped with 4 mm thick ceramic glass that is resistant to a thermal shock of 750 C Th...

Page 42: ...the product is kept efficient and ensure safe operation Thoroughly clean the combustion chamber and the heat exchanger Smoke motor cleaning dismantling and cleaning the smoke exhaust duct new silicon...

Page 43: ......

Page 44: ...aminox S r l Divisione Idro Zona Industriale Callarella 261 263 62028 SARNANO MC Italy Tel 39 0733 657 622 Fax 39 0733 657 494 www laminox com e mail export laminox com Termoboiler Mini rev 1 0 2019 E...

Reviews: