Combined Wind Sensor ARCO-Modbus
(14581) ARCO-Modbus
Manual
6.5
Instantaneous Values / Realtime Values (Input Register)
The following measured values are provided:
Register address Parameter name
Unit
Divisor
Quantity of registers
Access type
30001
Wind speed
m/s
10
1
Read only
30201
Wind direction
°
10
1
Read only
30401
Air temperature
°C
10
1
Read only
30601
Relative humidity
% r. F.
10
1
Read only
30701
Dew point
°C
10
1
Read only
30801
Air pressure
hPa
10
Read only
Example:
Retrieve wind speed
0D 04 75 31 00 01 7A C5 0D 04 02
00 1F
E8 F9
LEN
6
Transmission
Query =>
Source
Master
Dest
Slave 13
Function
Read Input Register (4)
Func Desk
Address=30001, Quantity of Register=1
Checksum
OK:C57A
LEN
5
Transmission
Response <=
Source
Slave 13
Dest
Master
Function
Read Input Register (4)
Func Desk
Byte count=2
Data
00 1F
Checksum
OK:F9E8
6.6
Period Data - Average, Maximum and Minimum (Input Register)
Register
Parameter name
Unit
Divisor
Quantity of registers Access type
30002
Wind speed average
m/s
10
1
Read only
30003
Wind speed maximum
m/s
10
1
Read only
30004
Wind speed minimum
m/s
10
1
Read only
30202
Wind direction average
°
10
1
Read only
30203
Wind direction maximum
°
10
1
Read only
30204
Wind direction minimum
°
10
1
Read only
30402
Air temperature average
°C
10
1
Read only
30403
Air temperature maximum
°C
10
1
Read only
30404
Air temperature minimum
°C
10
1
Read only
30602
Relative humidity average
% r. F.
10
1
Read only
30603
Relative humidity maximum
% r. F.
10
1
Read only
30604
Relative humidity minimum
% r. F.
10
1
Read only
30702
Dew point average
°C
10
1
Read only
30703
Dew point maximum
°C
10
1
Read only
30704
Dew point minimum
° C
10
1
Read only
30802
Air pressure average
hPa
10
1
Read only
30803
Air pressure maximum
hPa
10
1
Read only
30804
Air pressure minimum
hPa
10
1
Read only
The data are valid for the period between the current request and the previous request. The maximum range of a period is
1 hour. Recalling the average value of a minimum, maximum and average group will erase the appropriate registers.
Retrieve the values of a group in the sequence minimum, maximum, average.
Use command: 0x03
9