Lambrecht ARCO-Modbus 14581 Manual Download Page 9

Manual 

Combined Wind Sensor ARCO-Modbus

(14581) ARCO-Modbus

Manual

6.5 

Instantaneous Values / Realtime Values (Input Register)

The following measured values are provided:

Register address Parameter name

Unit

Divisor

Quantity of registers

Access type

30001

Wind speed

m/s

10

1

Read only

30201

Wind direction

°

10

1

Read only

30401

Air temperature

°C

10

1

Read only

30601

Relative humidity

% r. F. 

10

1

Read only

30701

Dew point

°C 

10

1

Read only

30801

Air pressure

hPa

10

Read only

Example:

 Retrieve wind speed

0D 04 75 31 00 01 7A C5 0D 04 02

00 1F

E8 F9

LEN 

6

Transmission 

Query =>

Source 

Master

Dest 

Slave 13

Function 

Read Input Register (4)

Func Desk 

Address=30001, Quantity of Register=1

Checksum 

OK:C57A

LEN 

5

Transmission 

Response <=

Source 

Slave 13

Dest 

Master

Function 

Read Input Register (4)

Func Desk 

Byte count=2

Data 

00 1F

Checksum 

OK:F9E8

6.6 

Period Data - Average, Maximum and Minimum (Input Register)

Register

Parameter name 

Unit 

Divisor

Quantity of registers Access type

30002 

Wind speed average

m/s 

10

1

Read only 

30003 

Wind speed maximum

m/s 

10

1

Read only 

30004 

Wind speed minimum

m/s 

10

1

Read only 

30202 

Wind direction average

° 

10

1

Read only 

30203 

Wind direction maximum

° 

10

1

Read only

30204 

Wind direction minimum

° 

10

1

Read only

30402

Air temperature average

°C

10

1

Read only

30403

Air temperature maximum

°C

10

1

Read only

30404

Air temperature minimum 

°C

10

1

Read only

30602

Relative humidity average

% r. F. 

10

1

Read only

30603

Relative humidity maximum

% r. F.

10

1

Read only

30604

Relative humidity minimum

% r. F. 

10

1

Read only

30702

Dew point average

°C 

10

1

Read only

30703

Dew point maximum 

°C 

10

1

Read only

30704

Dew point minimum 

° C 

10

1

Read only

30802

Air pressure average

hPa

10

1

Read only

30803

Air pressure maximum

hPa

10

1

Read only

30804

Air pressure minimum 

hPa

10

1

Read only

The data are valid for the period between the current request and the previous request. The maximum range of a period is 

1 hour. Recalling the average value of a minimum, maximum and average group will erase the appropriate registers. 
Retrieve the values of a group in the sequence minimum, maximum, average.
Use command: 0x03

9

Summary of Contents for ARCO-Modbus 14581

Page 1: ...g value of 0 3 m s Very large measuring range from 0 3 to 75 m s Quick and easy installation by pipe mounting and M12 plug connector Integrated regulated heater for optimal heating of the sensor heads...

Page 2: ...uipment Content 1 Introduction 3 2 Start Up 3 2 1 Installation Conditions 3 2 2 Tools and Installation Aids 3 2 3 Unpacking the Sensor 3 2 4 Goods Inspection 3 2 5 Power Supply 3 2 6 Mounting the Cup...

Page 3: ...luminum alloys The housing the cup rotor and the wind vane are anodized An electronically controlled sensor heating device allows for operation of the sensor over the wide range of 30 70 C 2 Start Up...

Page 4: ...d direction measurements the north mark on the sensor must be aligned with the geographical north direction To adjust the wind sensor in a firm and correct manner into the north direction this item is...

Page 5: ...cuitbreaker must be switched off It is not permitted for unauthorized persons to open the housing 3 Maintenance 3 1 Regular Maintenance and Calibration The sensors are very low maintenance and designe...

Page 6: ...Manual Combined Wind Sensor ARCO Modbus 14581 ARCO Modbus Manual 5 Dimensional Drawing and Electrical Connection ARCO Modbus 6...

Page 7: ...Manual Combined Wind Sensor ARCO Modbus 14581 ARCO Modbus Manual Electrical connection ARCO Modbus 7...

Page 8: ...e by the divisor Values of 9999 indicate an internal sensor error 6 3 Standard Configuration Default Baud rate 19200 Baud Byte frame 8E1 1 start bit 8 data bits 1 parity bit even parity 1 stop bit RTU...

Page 9: ...ss type 30002 Wind speed average m s 10 1 Read only 30003 Wind speed maximum m s 10 1 Read only 30004 Wind speed minimum m s 10 1 Read only 30202 Wind direction average 10 1 Read only 30203 Wind direc...

Page 10: ...d Input Register 4 Func Desk Byte count 2 Data 00 14 Checksum OK 3FB9 6 7 Descriptive Sensor Parameter Registers Holding Register Register Parameter name Quantity of registers Remark Access type 40050...

Page 11: ...01 06 48 05 10 9C 41 00 01 7E 09 LEN 9 Transmission Query Source Master Dest Slave 5 Function Write Multiple Register 16 Func Desk Address 40001 Quantity 1 Byte count 2 Register values 00 01 Checksum...

Page 12: ...ely Sensor cable 15 m 4 pole M12 plug Id No 32 14567 060010 various lengths possible Options 9340 Visualisation and evaluation software MeteoWare CS Basic Id No 36 09340 000000 Standards EMC EMI EN 60...