Lambrecht ARCO-Modbus 14581 Manual Download Page 10

Manual 

Combined Wind Sensor ARCO-Modbus

(14581) ARCO-Modbus

Manual

Example

: Retrieve wind speed (min. max. avr.) and erase the register content

01 04 75 34 00 01 6A 08 01 04 02

00 00

B9 30 01

04 75 33 00 01 DB C9 01 04 02

00 D6

38 AE 01 04

75 32 00 01 8A 09 01 04 02

00 14

B9 3F

LEN 

6

Transmission 

Query =>

Source 

Master

Dest 

Slave 1 

Function 

Read Input Register (4)

Func Desk 

Address=30004, Quantity of Register=1

Checksum 

OK:86A

LEN 

5

Transmission 

Response <=

Source 

Slave 1

Dest 

Master

Function 

Read Input Register (4)

Func Desk 

Byte count=2

Data

 

00 00

Checksum 

OK:30B9

LEN 

6

Transmission 

Query =>

Source 

Master

Dest 

Slave 1

Function 

Read Input Register (4)

Func Desk 

Address=30003, Quantity of Register=1

Checksum 

OK:C9DB

LEN 

5

Transmission 

Response <=

Source 

Slave 1

Dest 

Master

Function 

Read Input Register (4)

Func Desk 

Byte count=2

Data

 

00 D6

Checksum 

OK:AE38

LEN 

6

Transmission 

Query =>

Source 

Master

Dest 

Slave 1

Function 

Read Input Register (4)

Func Desk 

Address=30002, Quantity of Register=1

Checksum 

OK:98A

LEN 

5

Transmission 

Response <=

Source 

Slave 1

Dest 

Master

Function 

Read Input Register (4)

Func Desk 

Byte count=2

Data

 

00 14

Checksum 

OK:3FB9

6.7 

Descriptive Sensor Parameter Registers (Holding Register)

Register

Parameter name 

Quantity of registers

Remark

Access type

40050 

Device identification number 
(15 characters)

8 (2 characters in each 

register)

The returned data are 

in form of a 16 byte null 

terminated string

Read only

40100

Serial number
(11 characters)

6 (2 characters in each 

register)

The returned data are 

in form of a 12 byte null 

terminated string

Read only

40150 

Firmware version 
(up to 25 characters)

13 (2 characters in each 

register)

The returned data are 

in form of a 26 byte null 

terminated string

Read only

Example

: Retrieve the device identification number

(The identification number shown in the example is sensor-dependent. It is only used here for demonstration purposes).

0D 03 9C 72 00 08 CA 8B 0D 03 10

30 30 2E 31 36

                

00.16480.000130



34 38 30 2E 30 30 31 31 33 30 00

E8 6B

LEN 

6

Transmission 

Query =>

Source 

Master

Dest 

Slave 13

Function 

Read Holding Register (3)

Func Desk 

Address=40050, Quantity of Register=8

Checksum 

OK:8BCA

LEN 

19

Transmission 

Response <=

Source 

Slave 13

Dest 

Master

Function 

Read Holding Register (3)

Func Desk 

Byte count=16

Data

 

30 30 2E 31 36 34 38 30 2E 30 30 31 31 33 30 00

Checksum 

OK:6BE8

10

Summary of Contents for ARCO-Modbus 14581

Page 1: ...g value of 0 3 m s Very large measuring range from 0 3 to 75 m s Quick and easy installation by pipe mounting and M12 plug connector Integrated regulated heater for optimal heating of the sensor heads...

Page 2: ...uipment Content 1 Introduction 3 2 Start Up 3 2 1 Installation Conditions 3 2 2 Tools and Installation Aids 3 2 3 Unpacking the Sensor 3 2 4 Goods Inspection 3 2 5 Power Supply 3 2 6 Mounting the Cup...

Page 3: ...luminum alloys The housing the cup rotor and the wind vane are anodized An electronically controlled sensor heating device allows for operation of the sensor over the wide range of 30 70 C 2 Start Up...

Page 4: ...d direction measurements the north mark on the sensor must be aligned with the geographical north direction To adjust the wind sensor in a firm and correct manner into the north direction this item is...

Page 5: ...cuitbreaker must be switched off It is not permitted for unauthorized persons to open the housing 3 Maintenance 3 1 Regular Maintenance and Calibration The sensors are very low maintenance and designe...

Page 6: ...Manual Combined Wind Sensor ARCO Modbus 14581 ARCO Modbus Manual 5 Dimensional Drawing and Electrical Connection ARCO Modbus 6...

Page 7: ...Manual Combined Wind Sensor ARCO Modbus 14581 ARCO Modbus Manual Electrical connection ARCO Modbus 7...

Page 8: ...e by the divisor Values of 9999 indicate an internal sensor error 6 3 Standard Configuration Default Baud rate 19200 Baud Byte frame 8E1 1 start bit 8 data bits 1 parity bit even parity 1 stop bit RTU...

Page 9: ...ss type 30002 Wind speed average m s 10 1 Read only 30003 Wind speed maximum m s 10 1 Read only 30004 Wind speed minimum m s 10 1 Read only 30202 Wind direction average 10 1 Read only 30203 Wind direc...

Page 10: ...d Input Register 4 Func Desk Byte count 2 Data 00 14 Checksum OK 3FB9 6 7 Descriptive Sensor Parameter Registers Holding Register Register Parameter name Quantity of registers Remark Access type 40050...

Page 11: ...01 06 48 05 10 9C 41 00 01 7E 09 LEN 9 Transmission Query Source Master Dest Slave 5 Function Write Multiple Register 16 Func Desk Address 40001 Quantity 1 Byte count 2 Register values 00 01 Checksum...

Page 12: ...ely Sensor cable 15 m 4 pole M12 plug Id No 32 14567 060010 various lengths possible Options 9340 Visualisation and evaluation software MeteoWare CS Basic Id No 36 09340 000000 Standards EMC EMI EN 60...

Reviews: