15
4.4 Electrical connection of active 16131.5 series: wiring diagram
The instrument must be powered by an external power supply, providing an operating voltage in the
range from 8 to 30 VDC. This is the main power supply for the sensor, using the brown and white
wires.
Figure 4.4.1
:
Connector layout of 16131.5, indicating PIN numbers (viewed from cable side)
4.4.1
Wiring diagram 00.16131.501030 - Modbus RTU
Table 4.4.1.1
Wiring diagram of 00.16131.501030
PIN
WIRE
00.16131.501030
Modbus over RS-485
1
Brown
VDC [+]
2
White
VDC [−]
/ heater [-]
3
Blue
RS-485 B / B’ [+]
4
Black
RS-
485 A / A’[−]
5
Grey
heater [+]
Shield mesh
shield
Note 1: At the connector-end of the cable, the shield is connected to the connector housing.
Note 2: The heater is powered by applying a voltage to the grey wire, an operating voltage of 12 VDC
is used.
Note 3: Do not put more than 30 Volt across these wires, this will damage the sensor.
4.4.2
Wiring diagram 00.16131.501040 - Modbus RTU
Table 4.4.2.1
Wiring diagram of 00.16131.501040
PIN
WIRE
00.16131.501040
Modbus over TTL
00.16131.501040
4 to 20 mA output
1
Brown
On request
VDC [+]
2
White
not connected
3
Blue
4 to 20 mA output
4
Black
not connected
5
Grey
not connected
Shield mesh
shield
Note 1: At the connector-end of the cable, the shield is connected to the connector housing.