TAURA 24 MC W TOP
24
Key
B
Pressure
point
C
Modureg
cable
D
Protective
cap
E
Minimum pressure adjustment
G
Maximum pressure adjustment
Fig. 3
After checking or adjusting the pressure,
it is mandatory to seal the adjustment
screw with paint or a specific seal.
Adjusting the maximum heating output
To adjust the heating power, set the boiler on TEST operation (see par. 3.1). Turn the heating temperature control
knob (ref. 1 - fig. 1) clockwise to increase the power or anticlockwise to decrease it (see pressure/power diagram
chap. 4.5). Exit TEST operation (see par. 3.1). The maximum heating power will remain as set during the TEST.
Ignition power adjustment
To adjust the ignition power, set the boiler on TEST operation (see par. 3.1).
Turn the hot water temperature control knob (ref. 2 - fig. 1) clockwise to increase the power or anticlockwise to de-
crease it (see pressure/power diagram chap. 4.5). Exit TEST operation (see par. 3.1). The ignition power will remain
as set during the TEST.
Installer parameters menu
The card has 10 transparent parameters that can be modified either by Remote Control (Service parameters menu)
or by itself (8 from Installer Parameters Menu and 2 in Test Mode):
Remote Control Parameters Menu
Range
Default
Card menu
1 (not used)
/
/
/
2 (Gas type selection)
0=Natural gas,1=LPG
0=Natural gas
P1
3 (not used)
/
/
/
4 (Heating post-circulation pump)
1-20 minutes
6 minutes
P3
5 (Heating ramp)
1-20°C/min
5°C/min
P5
6 (Maximum heating output)
0-100%
100%
TEST mode
7 (Heating stand-by time)
0-255 seconds
120sec.
P2
8 (Maximum hot water user setpoint)
0=55°C,1=60°C
0
P6
9 (Ignition power)
0-60%
50 %
TEST mode
10 (Maximum heating user setpoint)
30-85°C
85°C
P4
11 (Switching off burner in hot water mode)
0=Fixed,1=Tied to setpoint
1=setp.
P7
12 (Mains Voltage Frequency)
0=50Hz,1=60Hz
0=50Hz
P8
The Remote Timer Control is modified by entering its Service parameters menu (see relevant manual): the order and
range correspond exactly to the contents of the table.
The card is modified in two ways.
The Maximum Heating Output and Ignition Power parameters can be modified in Test Mode (see relevant
paragraph).
The parameters, designated P1‚P8 in the previous table, can be displayed and if necessary modified from the Installer